Use of RF electric fields for simultaneous mineral and bio-fouling control in a heat exchanger

被引:13
作者
Kim, Wontae [1 ]
Cho, Daniel J. [2 ]
Cho, Young I. [1 ]
机构
[1] Drexel Univ, Dept Mech Engn & Mech, Philadelphia, PA 19104 USA
[2] Choson Res Corp, Eagleville, PA 19460 USA
关键词
Physical water treatment; Mineral fouling; Bio-fouling; RF electric fields; Cooling water; PHYSICAL WATER-TREATMENT; MITIGATION;
D O I
10.1016/j.icheatmasstransfer.2011.05.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
The objective of the present study was to investigate the effectiveness of a physical water treatment (PWT) technology using oscillating RF (radio frequency) electric fields in water to mitigate both mineral and bio-fouling in a cooling water application. Heat transfer tests were conducted using a laboratory-scale cooling tower to determine fouling resistance over time, and bio-fouling tests were performed using a heterotrophic plate count method to measure colony forming units (CFU) values per milliliter of cooling water. The results indicated that the present PWT technology could provide an effective mineral fouling prevention by maintaining 90% of the peak heat transfer performance of a heat exchanger, while effectively controlling water-borne microbial organisms. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1003 / 1007
页数:5
相关论文
共 20 条
[1]  
[Anonymous], 1953, MECH ENG
[2]  
[Anonymous], ASHRAE T
[3]   Magnetic amelioration of scale formation [J].
Baker, JS ;
Judd, SJ .
WATER RESEARCH, 1996, 30 (02) :247-260
[4]   Electro-flocculation mechanism of physical water treatment for the mitigation of mineral fouling in heat exchangers [J].
Cho, Y. I. ;
Kim, W. T. ;
Cho, D. J. .
EXPERIMENTAL HEAT TRANSFER, 2007, 20 (04) :323-335
[5]  
Cho Y.I., 2004, Advances in Heat Transfer, V38, P1, DOI [10.1016/S0065-2717(04)38001-9, DOI 10.1016/S0065-2717(04)38001-9]
[6]   Pulsed-power treatment for physical water treatment [J].
Cho, YI ;
Lane, J ;
Kim, W .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2005, 32 (07) :861-871
[7]  
Cowan J. C., 1976, WATER FORMED SCALE D, P412
[8]  
Eaton AD, 2009, STANDARD METHODS EXA
[9]  
Engstrom G.G., 1994, TP9404 COOL TECHN I
[10]   Killing of microorganisms by pulsed electric fields [J].
Grahl, T ;
Markl, H .
APPLIED MICROBIOLOGY AND BIOTECHNOLOGY, 1996, 45 (1-2) :148-157