Transfer characteristic correlations given in the literature for wet-cooling tower fills are generally only a function of the air and water mass flow rates. This is a gross simplification of a very complex heat and mass transfer (evaporative cooling) process. In addition to the effects of the air and water mass flow rates, effects of the inlet water temperature, air drybulb temperature, wetbulb temperature, and fill height on the transfer characteristic, or Merkel number are investigated in the present study. The accuracy of two different empirical equations is also evaluated. It is found that the transfer characteristic correlations for wet-cooling tower fills are functions of the inlet water temperature and fill height but not of the air drybulb and wetbulb temperatures.
引用
收藏
页码:35 / 41
页数:7
相关论文
共 22 条
[1]  
BAARD TW, 1998, THESIS U STELLENBOSC
[2]  
BAKER DR, 1961, T ASME, P339
[3]  
Beckwith T. G., 1993, MECH MEASUREMENTS
[4]  
*BRIT STAND I, 1988, WAT COOL TOW 2
[5]   Electrical microstimulation of cortical area MST biases heading perception in monkeys [J].
Britten, KH ;
van Wezel, RJA .
NATURE NEUROSCIENCE, 1998, 1 (01) :59-63
[6]  
*COOL TOW I COD TO, 1990, STAND SPEC ACC TEST
[7]  
*CTI, 1967, COOL TOW PERF CURV
[8]   The investigation of cooling tower packing in various arrangements [J].
Goshayshi, HR ;
Missenden, JF .
APPLIED THERMAL ENGINEERING, 2000, 20 (01) :69-80
[9]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843
[10]  
JOHNSON BM, 1989, COOLING TOWER PERFOR, V2