Failure analysis of transmission line tower subjected to combined wind and dust loads

被引:2
|
作者
Salaam, Shaik Esub [1 ]
Rao, N. Prasad [2 ]
Raju, P. Krishnam [1 ]
机构
[1] Gayatri Vidya Parishad Coll Engn Autonomous, Dept Civil Engn, Visakhapatnam 530048, Andhra Pradesh, India
[2] CSIR Struct Engn Res Ctr, Chennai 600113, Tamil Nadu, India
来源
CURRENT SCIENCE | 2021年 / 121卷 / 04期
关键词
Dust storms; failure analysis; power supply; transmission line towers; COLLAPSE ANALYSIS; SYSTEM;
D O I
10.18520/cs/v121/i4/511-520
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Towers play a vital role in the transmission line (TL) system. The main objective of the present study is to analyse the failure of towers subjected to dust storms. This study, analyses the failure of a 765 kV single-circuit delta-type horizontal configuration tower in the river delta region near Agra. TL towers are designed based on IS 802 Part 1/Sec 1 and 2 standards. Dust particles of soil may be lighter individually, but have definite density. The wind carrying dust particles may increase the wind pressure on the tower line system. The increased wind pressure significantly affects the sag and tension of ground wire and conductor and results in additional loads on the tower, thus causing failure. It also increases wind load on the tower body and insulator string. There is literature related to numerical and wind tunnel studies on the combined effect of wind and rain loads, but no information is available on the wind and dust loads at present. The density variation method is used in the present study for calculation of additional wind pressure due to dust particles during storms. A relation between density of air mix, volume fraction of dust and density of dust particles is considered. Using FEM software, the tower is analysed for existing design loads and verified for its strength adequacy. The tower stability is studied by analysing for additional loads considering the presence of dust particles in the wind for three different volume fractions of 0.01%/m(3), 0.02%/m(3) and 0.03%/m(3). The wind pressure increases by about 10% for an increase of every 0.01% of dust particles in the wind. The tension in the conductor and ground wire increases by 8%. The existing tower design is inadequate to withstand the additional forces from wind storms associated even with a small fraction of dust particles and may be the reason for the failure of towers in northern India during a particular period of the year.
引用
收藏
页码:511 / 520
页数:10
相关论文
共 50 条
  • [21] High-voltage transmission tower-line system subjected to disaster loads
    Li Hongnan
    Bai Haifeng
    PROGRESS IN NATURAL SCIENCE-MATERIALS INTERNATIONAL, 2006, 16 (09) : 899 - 911
  • [22] Fragility analysis of a long-span transmission tower-line system under wind loads
    Tian, Li
    Zhang, Xin
    Fu, Xing
    ADVANCES IN STRUCTURAL ENGINEERING, 2020, 23 (10) : 2110 - 2120
  • [23] Velocity Ratio of Wind-Driven Rain and Its Application on a Transmission Tower Subjected to Wind and Rain Loads
    Tian, Li
    Zeng, Yu-Jie
    Fu, Xing
    JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES, 2018, 32 (05)
  • [24] Safety Analysis of Transmission Tower Subjected to Different Levels of Wind Loading
    Yang, Yunzheng
    2020 3RD INTERNATIONAL CONFERENCE ON APPLIED MATHEMATICS, MODELING AND SIMULATION, 2020, 1670
  • [25] Fragility Analysis of Transmission Line Subjected to Wind Loading
    Fu, Xing
    Li, Hong-Nan
    Tian, Li
    Wang, Jia
    Cheng, Hu
    JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES, 2019, 33 (04)
  • [26] Fragility of transmission tower-line system subjected to concurrent wind and ice accretion
    Xiao, M. Y.
    Zhou, W. X.
    Bitsuamlak, G.
    Hong, H. P.
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2024, 222
  • [27] ANALYSIS OF POSTBUCKLING BEHAVIOR OF LINE PIPE SUBJECTED TO COMBINED LOADS
    ZHOU, ZL
    MURRAY, DW
    INTERNATIONAL JOURNAL OF SOLIDS AND STRUCTURES, 1995, 32 (20) : 3015 - &
  • [28] Collapse Mechanism of Transmission Tower Subjected to Strong Wind Load and Dynamic Response of Tower-Line System
    Li, Junkuo
    Gao, Fan
    Wang, Lihuan
    Ren, Yaning
    Liu, Chuncheng
    Yang, Aiquan
    Yan, Zhao
    Jiang, Tao
    Li, Chengbo
    ENERGIES, 2022, 15 (11)
  • [29] Wind Tunnel Test for Wind Loads of Transmission Tower Leg in Skew Wind
    Hu X.
    Zhang D.
    Song X.
    Deng H.
    Tongji Daxue Xuebao/Journal of Tongji University, 2022, 50 (04): : 511 - 517
  • [30] Failure Analysis of a Cruciform-Leg Transmission Line Tower
    Veerendra Kumar Shukla
    Munusamy Selvaraj
    Kalla Vijaya Kumar
    International Journal of Steel Structures, 2021, 21 : 539 - 548