Spurious activation and operational integrity evaluation of redundant safety instrumented systems
被引:0
作者:
Meng Qi
论文数: 0引用数: 0
h-index: 0
机构:
Yonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South KoreaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Meng Qi
[1
]
Kan Yufeng
论文数: 0引用数: 0
h-index: 0
机构:
China Univ Petr East China, Coll Elect & Mech Engn, Qingdao 266580, Peoples R ChinaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Kan Yufeng
[2
]
Li Xun
论文数: 0引用数: 0
h-index: 0
机构:
China Univ Petr East China, Coll Elect & Mech Engn, Qingdao 266580, Peoples R ChinaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Li Xun
[2
]
Wang Xiaoying
论文数: 0引用数: 0
h-index: 0
机构:
China Univ Petr East China, Coll Elect & Mech Engn, Qingdao 266580, Peoples R ChinaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Wang Xiaoying
[2
]
Zhao Dongfeng
论文数: 0引用数: 0
h-index: 0
机构:
China Univ Petr East China, Coll Chem Engn, Qingdao 266580, Peoples R ChinaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Zhao Dongfeng
[3
]
Il, Moon
论文数: 0引用数: 0
h-index: 0
机构:
Yonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South KoreaYonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
Il, Moon
[1
]
机构:
[1] Yonsei Univ, Dept Chem & Biomol Engn, 50 Yonsei Ro, Seoul 03722, South Korea
[2] China Univ Petr East China, Coll Elect & Mech Engn, Qingdao 266580, Peoples R China
[3] China Univ Petr East China, Coll Chem Engn, Qingdao 266580, Peoples R China
Safety instrumented system (SIS);
Spurious activation;
Spurious trip rate (STR);
Common cause failure (CCF);
Optimal configurations;
DESIGN OPTIMIZATION;
REQUIREMENTS;
SUBJECT;
GAS;
D O I:
10.1016/j.ress.2019.106785
中图分类号:
T [工业技术];
学科分类号:
08 ;
摘要:
Safety instrumented systems (SISs) used in various industries are designed to perform specific safety functions to prevent possible accident scenarios. However, spurious activation occurs when a SIS is activated in an untimely manner, potentially resulting in production interruption, economic loss as well as risk to present during the system restoration. Therefore, it is necessary to quantify the spurious activation rate to reduce the number of spurious activations and achieve the highest overall level of risk reduction. This study analyzes possible scenarios leading to a spurious trip in SIS subsystems and presents a further development of existing analytical formulas to calculate the spurious trip rate (STR) for any KooN configuration. The proposed formulas are compared to the existing ones to evidence the improvements and are applied in numerical calculations to investigate the operational integrity of SIS subsystems. Results indicate that common cause failure contributes to most of the STR in input elements and logic solvers, and optimal configurations with both lower PFDavg and lower STR are identified in each subsystem. The overall approach is illustrated via a simple case study and some conclusions are drawn.