Bed configuration effects on the finned flat-tube adsorption heat exchanger performance: Numerical modeling and experimental validation

被引:58
作者
Kowsari, Milad Mohammadzadeh [1 ]
Niazmand, Hamid [1 ]
Tokarev, Mikhail Mikhailovich [2 ]
机构
[1] FUM, Dept Mech Engn, Mashhad, Iran
[2] Russian Acad Sci, Boreskov Inst Catalysis, Pr Lavrentieva 5, Novosibirsk 630090, Russia
关键词
Adsorption cooling; Flat-tube heat exchanger; Trapezoidal fin; Rectangular fin; Distributed parameters model; LOOSE GRAINS CONFIGURATION; SELECTIVE WATER SORBENTS; ADSORBENT BED; MASS-TRANSFER; WORKING PAIR; MANAGEMENT STRATEGY; COOLING SYSTEMS; CHILLER; OPTIMIZATION; DYNAMICS;
D O I
10.1016/j.apenergy.2017.11.019
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A three dimensional numerical scheme has been developed to examine geometrical configuration effects on the performance of a single bed adsorption chiller with a trapezoidal aluminum finned flat-tube heat exchanger (FFT HEx). A mathematical distributed model along with the linear driving force (LDF) model and Darcy's law have been considered to take into account the effects of heat and both intra/inter-grain mass transfer resistances. The developed numerical scheme has also been validated experimentally by using a composite sorbent SWS-1L and water as a working pair. Additionally, rectangular beds with identical working conditions and bed dimensions as the tested trapezoidal beds have been examined in similar details to identify, which type of the fin geometry provides a superior performance. It was found that in this particular HEx, the heat transfer resistance is mainly influenced by both of the fin pitch and height, while the inter-grain mass transfer resistance is independently controlled by the bed length. This fact makes the role of the fin pitch and fin height almost interchangeable with respect to the cycle time and specific cooling power (SCP) especially in rectangular beds. However, the coefficient of performance (COP) is more influenced by the fin height than the fin pitch. In addition, higher SCP can be achieved at smaller bed dimensions at the expense of lower COP. Moreover, it was found that using rectangular bed is more appropriate, since its SCP is either the same or higher than its corresponding trapezoidal bed especially at shorter bed lengths, while COP remains almost the same for both bed types in all considered ranges of bed dimensions. Finally, a bed designing procedure has been proposed for proper designing of effective adsorption HExs based on the performed parametric studies.
引用
收藏
页码:540 / 554
页数:15
相关论文
共 52 条
[1]   Heat exchanger design effect on the system performance of silica gel adsorption refrigeration systems [J].
Alam, KCA ;
Saha, BB ;
Kang, YT ;
Akisawa, A .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2000, 43 (24) :4419-4431
[2]  
[Anonymous], 2007, TRANSPORT PHENOMENA
[3]  
Aristov Y., 1997, Russian Journal of Physical Chemistry A, V71, P327
[4]   Selective water sorbents for multiple applications .1. CaCl2 confined in mesopores of silica gel: Sorption properties [J].
Aristov, YI ;
Tokarev, M ;
Cacciola, G ;
Restuccia, G .
REACTION KINETICS AND CATALYSIS LETTERS, 1996, 59 (02) :325-333
[5]  
ARISTOV YI, 1997, RUSS J PHYS CHEM, V71, P197
[6]   Reallocation of adsorption and desorption times for optimisation of cooling cycles [J].
Aristov, Yu. I. ;
Sapienza, A. ;
Ovoshchnikov, D. S. ;
Freni, A. ;
Restuccia, G. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (03) :525-531
[7]   Experimental and numerical study of adsorptive chiller dynamics: Loose grains configuration [J].
Aristov, Yuri I. .
APPLIED THERMAL ENGINEERING, 2013, 61 (02) :841-847
[8]   Optimization of adsorption dynamics in adsorptive chillers: Loose grains configuration [J].
Aristov, Yuriy I. ;
Glaznev, Ivan S. ;
Girnik, Ilya S. .
ENERGY, 2012, 46 (01) :484-492
[9]   Adsorptive transformation of heat: Principles of construction of adsorbents database [J].
Aristov, Yuriy I. .
APPLIED THERMAL ENGINEERING, 2012, 42 :18-24
[10]   Optimal adsorbent for adsorptive heat transformers: Dynamic considerations [J].
Aristov, Yuriy I. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (04) :675-686