Intensification of heat exchangers performance by modified and optimized twisted tapes

被引:53
|
作者
Hasanpour, A. [1 ]
Farhadi, M. [1 ]
Sedighi, K. [1 ]
机构
[1] Babol Noshirvani Univ Technol, Fac Mech Engn, Babol Sar, Iran
关键词
Optimization; Twisted tape; Corrugated tube; Genetic Algorithm; Artificial neural network; ARTIFICIAL NEURAL-NETWORKS; FRICTION FACTOR CHARACTERISTICS; TRANSFER ENHANCEMENT; CORRUGATED TUBES; TURBULENT-FLOW; PRESSURE-DROP; DESIGN; EFFICIENCY; INSERTS; LAMINAR;
D O I
10.1016/j.cep.2017.07.026
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an application of artificial neural networks together with genetic algorithm on experimental tests to optimization and intensification the thermo-hydraulic behavior of a corrugated tube heat exchanger equipped with twisted tapes. The experiments on conventional, perforated, V-cut and U-cut twisted tape inserts are done on turbulent regimes with Reynolds numbers from 5000 to 15000 while the twist ratios are 3, 5 and 7. Finally, the results are optimized using multi-objective genetic algorithm to find out the optimal cases for thermal performance factor (R3). The average differences between the artificial neural network prediction and experimental results are found very low and even less than 2%. The results show that the corrugated tube with V-cut twisted tape has the maximum heat transfer rate while the minimum pressure drop belongs to the perforated twisted tape. Also the thermal performance factor is always more than one and the maxima is happened at V-cut twisted tape with R3 = 1.50.
引用
收藏
页码:276 / 285
页数:10
相关论文
共 50 条