Experimental Studies of influence of DC and AC Electric Fields on Bridging in Contaminated Transformer Oil

被引:68
作者
Mahmud, S. [1 ]
Chen, G. [1 ]
Golosnoy, I. O. [1 ]
Wilson, G. [2 ]
Jarman, P. [2 ]
机构
[1] Univ Southampton, Sch Elect & Comp Sci, Southampton SO17 1BJ, Hants, England
[2] Natl Grid, Warwick CV34 6DA, England
基金
英国工程与自然科学研究理事会;
关键词
HVDC transformer; failure; contamination; Dielectrophoresis; drag force; bridging; IMPURITY PARTICLES; COMPUTER-SIMULATION; CHARGE; MOTION;
D O I
10.1109/TDEI.2014.004573
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Analysis of real operating condition revealed that HVDC transformers experience combined effect of DC biased AC electric field. The dynamics of pressboard particle in contaminated transformer oil under the influence of DC, AC and DC biased AC electric field has been investigated in this paper. Different levels of particle concentrations are tested at different applied voltages. Optical images of the particles accumulation together with conduction current have been recorded during the experiments. A complete bridge between the electrodes of cellulose particles were observed for all the tests carried out under DC and DC biased AC electric field. Opposite to that, for AC experiments, pressboard particles accumulated on surfaces of both electrodes but did not create a full bridge between the electrodes. It is concluded that a combination of DC and AC voltages in a HVDC transformer could lead to a bridge formation within the equipment which could cause failure.
引用
收藏
页码:152 / 160
页数:9
相关论文
empty