Numerical studies on fire hazards of elevator evacuation in supertall buildings

被引:20
作者
Cai, N. [1 ]
Chow, W. K. [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Res Ctr Fire Engn, Hong Kong, Peoples R China
关键词
Elevator; Evacuation time; Supertall buildings; Smoke extraction; Smoke spread; Computational fluid dynamics; Fire safety; Pressurization system; HEAT RELEASE RATE; SHAFT PRESSURIZATION; SMOKE CONTROL; SIMULATION;
D O I
10.1177/1420326X17751593
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Long evacuation time is a key fire safety concern for crowded supertall buildings. Elevator evacuation appears to be the only choice but fire safety provisions are not specially designed for the use of elevators. A fire safe elevator system was proposed earlier for supertall buildings by providing elevator accessible on each floor level and passing through the refuge place. The fire hazard associated with this design has been studied numerically through an example building in this paper. Smoke spread to the elevator system was considered in the study. The effect of ventilation of the shaft, stack effect and wind effect on smoke movement were studied by empirical equations in fire engineering and justified by computational fluid dynamics. Different designs of smoke extraction with pressurization system were evaluated by analysing the smoke dispersion and pressure distributions. The effect of fire at different heights on smoke spread was also investigated. Results show that the smoke extraction system can only delay smoke spread to the elevator shaft near the fire source for a short time. The "four-floor approach" pressurization system can confine the smoke in the area of fire floor for a sufficiently long time period for safe evacuation.
引用
收藏
页码:247 / 263
页数:17
相关论文
共 28 条
[1]  
[Anonymous], 2003, 81722003 BS EN
[2]  
[Anonymous], 2012, INT BUILD COD
[3]   Smoke movement in elevator shafts during a high-rise structural fire [J].
Black, W. Z. .
FIRE SAFETY JOURNAL, 2009, 44 (02) :168-182
[4]  
Buildings Department, 2011, COD PRACT BUILD WORK
[5]   Numerical Studies on Heat Release Rate in Room Fire on Liquid Fuel under Different Ventilation Factors [J].
Cai, N. ;
Chow, W. K. .
INTERNATIONAL JOURNAL OF CHEMICAL ENGINEERING, 2012, 2012
[6]   Numerical studies on heat release rate in a room fire burning wood and liquid fuel [J].
Cai, Na ;
Chow, Wan-ki .
BUILDING SIMULATION, 2014, 7 (05) :511-524
[7]   Wind tunnel and CFD studies on wind flow around a high-rise building with a refuge floor [J].
Cheng, CCK ;
Lam, KM ;
Yuen, RKK ;
Lo, SM .
Tall Buildings: From Engineering to Sustainability, 2005, :435-441
[8]   Heat release rate of accidental fire in a supertall building residential flat [J].
Chow, C. L. ;
Chow, W. K. .
BUILDING AND ENVIRONMENT, 2010, 45 (07) :1632-1640
[9]  
Chow CL, 2009, FIRE SAFE
[10]   Fuel Load and Peak Heat Release Rate Correlations in Post-Flashover Room Fires [J].
Chow, W. K. .
HEAT TRANSFER ENGINEERING, 2010, 31 (03) :250-254