A Study on a Control Method with a Ventilation Requirement of a VAV System in Multi-Zone

被引:14
作者
Kim, Hyo-Jun [1 ]
Cho, Young-Hum [2 ]
机构
[1] Yeungnam Univ, Grad Sch, Dept Architectural Engn, 280 Daehak Ro, Gyongsan 38541, Gyeongbuk, South Korea
[2] Yeungnam Univ, Sch Architecture, 280 Daehak Ro, Gyongsan 38541, Gyeongbuk, South Korea
关键词
VAV system; terminal unit; TRNSYS; control method; multi-zone; ventilation requirement; MINIMUM AIR-FLOW; DEMAND-CONTROLLED VENTILATION; CONDITIONING SYSTEMS; TEMPERATURE; DAMPERS;
D O I
10.3390/su9112066
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The objective of this study was to propose a control method with a ventilation requirement of variable air volume (VAV) system in multi-zone. In order to control the VAV system inmulti-zone, it is essential to control the terminal unit installed in each zone. A VAV terminal unit with conventional control method using a fixed minimum air flow can cause indoor air quality (IAQ) issues depending on the variation in the number of occupants. This research proposes a control method with a ventilation requirement of the VAV terminal unit and AHU inmulti-zone. The integrated control method with an air flow increase model in the VAV terminal unit, AHU, and outdoor air intake rate increase model in the AHU was based on the indoor CO2 concentration. The conventional and proposed control algorithms were compared through a TRNSYS simulation program. The proposed VAV terminal unit control method satisfies all the conditions of indoor temperature, IAQ, and stratification. An energy comparison with the conventional control method showed that the method satisfies not only the indoor thermal comfort, IAQ, and stratification issue, but also reduces the energy consumption.
引用
收藏
页数:17
相关论文
共 25 条
  • [21] A review of recent developments and technological advancements of variable-air-volume (VAV) air-conditioning systems
    Okochi, Godwine Swere
    Yao, Ye
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 59 : 784 - 817
  • [22] Demand controlled ventilation - A case study for existing Swedish multifamily buildings
    Pavlovas, V
    [J]. ENERGY AND BUILDINGS, 2004, 36 (10) : 1029 - 1034
  • [23] Air handling unit supply air temperature optimal control during economizer cycles
    Wang, Gang
    Song, Li
    [J]. ENERGY AND BUILDINGS, 2012, 49 : 310 - 316
  • [24] Evaluation program for the energy-saving of variable-air-volume systems
    Yao, Ye
    Lian, Zhiwei
    Liu, Weiwei
    Hou, Zhijian
    Wu, Ming
    [J]. ENERGY AND BUILDINGS, 2007, 39 (05) : 558 - 568
  • [25] Energy analysis on VAV system with different air-side economizers in China
    Yao, Ye
    Wang, Li
    [J]. ENERGY AND BUILDINGS, 2010, 42 (08) : 1220 - 1230