Particularities of Exergy Analysis in Air Conditioning Systems

被引:0
作者
Prokhorov, V., I [1 ]
Troyanchuk, S., V [1 ]
Razakov, M. A. [2 ]
机构
[1] Moscow State Univ Civil Engn, Moscow, Russia
[2] Moscow Power Engn Inst, 14 Krasnokazarmennaya Str, Moscow 111250, Russia
来源
SCIENCE & TECHNIQUE | 2022年 / 21卷 / 01期
关键词
exergy; exergy chart; h-d-diagram; air conditioning; energy saving; moist air; energy; ENERGY;
D O I
10.21122/2227-1031-2022-21-1-42-49
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The paper examines two methods of choosing the initial reference point for exergy of the moist air flow. The first method is characterized by a zero exergy value at the current temperature and humidity of the outdoor air, which are variable both in daily and annual periods. Another is characterized by constant values of parameters of moist indoor air (its temperature and humidity in the room). A comparative study has shown the advantages of the second method: greater stability of values in air processing processes and their convenient presentation on exergy chart. However, it should be noted that this method provides a non-standard technical representation in which the entire energy flow is reduced to zero. The climatic information (temperature and humidity of the outside air) for numerical-analytical experiment has been used from official open sources. The city where the air conditioning system was supposedly installed is Stavropol. The research has been carried out in the summer and cold periods of the year. It is assumed that there are not installed any large heat sources in the room and the main heat sources appeared depending on the period of the year. Additionally, the air conditioning system was equipped with a recirculation line from the serviced room with a mechanical ventilator. The recirculated air entered the mixing chamber in the air conditioning unit which is reducing the consumption of heat energy in the cold season. There are the processes of air conditioning on the Ramzin's h-d-diagram for warm and cold operational modes of air conditioning unit, the air conditioning system under consideration.
引用
收藏
页码:42 / 49
页数:8
相关论文
共 18 条
[1]   Building energy metering and environmental monitoring - A state-of-the-art review and directions for future research [J].
Ahmad, Muhammad Waseem ;
Mourshed, Monjur ;
Mundow, David ;
Sisinni, Mario ;
Rezgui, Yacine .
ENERGY AND BUILDINGS, 2016, 120 :85-102
[2]   Effect of reference state characteristics on the Thermal Exergy analysis of a building [J].
Baldi, Marta Giulia ;
Leoncini, Lorenzo .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :177-186
[3]   Thermal Exergy analysis of a building [J].
Baldi, Marta Giulia ;
Leoncini, Lorenzo .
6TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, 2014, 62 :723-732
[4]  
Brodyansky V. M., 1973, EXERGY METHOD THERMO, V296
[5]  
Dincer I., 2010, Thermal energy storage: Systems and applications, V2nd, DOI [10.1002/9780470970751, DOI 10.1002/9780470970751]
[6]  
Dincer I, 2013, EXERGY: ENERGY, ENVIRONMENT AND SUSTAINABLE DEVELOPMENT, 2ND EDITION, P363, DOI 10.1016/B978-0-08-097089-9.00018-8
[7]   Experimental research of thermal comfort conditions in small test buildings with different types of heating [J].
Gendelis, Stanislavs ;
Jakovics, Andris ;
Bandeniece, Liene .
6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 :2929-2934
[8]   Comparative study on thermal environment and energy consumption of urban residential houses in Beijing [J].
Luo, Qinzi ;
Yang, Le ;
Liu, NianXiong ;
Xia, Jianjun .
9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 :2141-2148
[9]   Development of the Energy-Saving Air Regeneration System in Production Rooms [J].
Minkin, M. S. ;
Kuimov, D. N. ;
Lukyanov, A. D. .
2ND INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING (ICIE-2016), 2016, 150 :1353-1358
[10]   Experimental study of air conditioning control system for building energy saving [J].
Nasution, Henry ;
Sumeru, K. ;
Aziz, Azhar Abdul ;
Senawi, Mohd. Yusoff .
INTERNATIONAL CONFERENCE ON APPLIED ENERGY, ICAE2014, 2014, 61 :63-66