A Modified McQuiston model for evaluating efficiency of wet fin considering effect of condensate film moving on fin surface

被引:14
作者
Xu, Xiangguo [1 ]
Xia, Liang [1 ]
Chan, Mingyin [1 ]
Deng, Shiming [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
wet fin efficiency; moving condensate film; total condensing rate; governing equation;
D O I
10.1016/j.enconman.2008.01.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
A modified McQuiston model for evaluating the wet fin efficiency of cooling and dehumidification coils has been developed by modifying the existing popular McQuiston model and is reported in this paper. The condensate film moving on fin surfaces and its impacts on heat transfer have been taken into account in deriving the governing equation for fin temperature, and consequently, the enthalpy change of the moving condensate film has been included in the governing equation for fin temperature. The modified McQuiston model was validated by comparing its predictions with those using the McQuiston model under the same operating and boundary conditions. It is expected that the modified McQuiston model developed can be applied not only to the commonly seen air cooling and dehumidification but also to certain special operations such as industrial steam condensation. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2403 / 2408
页数:6
相关论文
共 16 条
[1]  
[Anonymous], 1994, BUILD ENG
[2]   VERTICAL FIN EFFICIENCY WITH FILM CONDENSATION [J].
BURMEISTER, LC .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1982, 104 (02) :391-393
[3]   Mass transfer (absorption) coefficients - Prediction from data on great transfer and fluid friction [J].
Chilton, TH ;
Colburn, AP .
INDUSTRIAL AND ENGINEERING CHEMISTRY, 1934, 26 :1183-1187
[4]  
Elmandy AH, 1983, ASHRAE T 1A, V89, P135
[5]   Condensation of downward-flowing HFC134a in a staggered bundle of horizontal finned tubes: effect of fin geometry [J].
Honda, H ;
Takata, N ;
Takamatsu, H ;
Kim, JS ;
Usami, K .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (01) :3-10
[6]  
HONG TK, 1996, HVAC&R RES, V2, P27
[7]  
Kern D., 1972, EXTENDED SURFACE HEA
[8]   An analytical study of the effect of dehumidification of air on the performance and optimization of straight tapered fins [J].
Kundu, B .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2002, 29 (02) :269-278
[9]   An experimental study on the inherent operational characteristics of a direct expansion (DX) air conditioning (A/C) unit [J].
Li, Zheng ;
Deng, Shiming .
BUILDING AND ENVIRONMENT, 2007, 42 (01) :1-10
[10]  
McQuiston FC., 1994, HEATING VENTILATING