MODIFIED OPERATING PARAMETER-BASED IYER CORRELATION FOR THE COEFFICIENT OF PERFORMANCE (COP) PREDICTION OF DIFFERENT FLUID PAIRS IN DOUBLE-EFFECT VAPOR ABSORPTION REFRIGERATION (VAR) CYCLES

被引:0
作者
Khan, Muhammad Saad [1 ]
Kadam, Sambhaji T. [1 ]
Kyriakides, Alexios-Spyridon [2 ]
Hassan, Ibrahim [1 ]
Papadopoulos, Athanasios I. [2 ]
Rahman, Mohammad Azizur [1 ]
Seferlis, Panos [3 ]
机构
[1] Texas A&M Univ Qatar, Dept Mech Engn, Doha, Qatar
[2] Ctr Res & Technol Hellas, Chem Proc & Energy Resources Inst, Thessaloniki, Greece
[3] Aristotle Univ Thessaloniki, Dept Mech Engn, Thessaloniki, Greece
来源
PROCEEDINGS OF ASME 2021 FLUIDS ENGINEERING DIVISION SUMMER MEETING (FEDSM2021), VOL 2 | 2021年
关键词
COP; double effect VAR cycle; Error analysis; performance-based correlations; SYSTEMS; SIMULATION; SERIES; SINGLE;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Vapor absorption refrigeration (VAR) is a sustainable alternative to the conventional vapor compression refrigeration (VCR) cycle, owing to its lower non-renewable energy requirements and potentially for exploitation of renewable energy sources. Traditionally, the coefficient of performance (COP) of the conventional single effect VAR cycle is considerably lower than VCR cycles. This provides room for improvement which can be attained through double effect VAR cycles that provide relatively higher performance. The COP of the dual effect VAR cycle is enhanced due to the waste/rejected heat energy utilization from the condenser or the absorber into a secondary generator. Models that correlate the COP of the double effect VAR cycle with operating parameters are not available in the open literature, with Iyer's correlation being the only exception. This work applies this COP correlation using literature data for double effect VAR that operate with a variety of refrigerant and absorbent pairs. A comprehensive Mean Absolute Percentage Error (MAPE) analysis is performed for more than 2028 data points of various fluid pairs. Results reveal that MAPE (86.6- 839%) values appear to be quite high for the reported correlation. Furthermore, the model is optimized using the proposed data set, considerably reducing the MAPE up to 36.03%. The results also indicate that due to the lack of fluid-specific parameters, the application of this correlation may not support the development of new double effect VAR cycles. Therefore, it is crucial to establish a performance-based correlation that considers both operational parameters and fluid parameters to assess the performance of new and efficient dual effect VAR cycles
引用
收藏
页数:6
相关论文
共 25 条
  • [1] Arun MB, 1998, INT J ENERG RES, V22, P1001, DOI 10.1002/(SICI)1099-114X(199809)22:11<1001::AID-ER428>3.0.CO
  • [2] 2-C
  • [3] First and Second Law Analyses of Double Effect Parallel and Series Flow Direct Fired Absorption Cycles for Optimum Operating Parameters
    Azhar, Md.
    Siddiqui, M. Altamush
    [J]. JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2019, 141 (12):
  • [4] Optimization of operating temperatures in the gas operated single to triple effect vapour absorption refrigeration cycles
    Azhar, Md
    Siddiqui, M. Altamush
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 82 : 401 - 425
  • [5] Thermodynamic investigation of LiCl-H2O working pair in a double effect absorption chiller driven by parabolic trough collectors
    Bellos, Evangelos
    Tzivanidis, Christos
    Pavlovic, Sasa
    Stefanovic, Velimir
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2017, 3 : 75 - 87
  • [6] Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture
    Dominguez-Inzunza, L. A.
    Hernandez-Magallanes, J. A.
    Sandoval-Reyes, M.
    Rivera, W.
    [J]. APPLIED THERMAL ENGINEERING, 2014, 66 (1-2) : 612 - 620
  • [7] Sustainable District Cooling Systems: Status, Challenges, and Future Opportunities, with Emphasis on Cooling-Dominated Regions
    Eveloy, Valerie
    Ayou, Dereje S.
    [J]. ENERGIES, 2019, 12 (02):
  • [8] Ammonia lithium nitrate and ammonia sodium thiocyanate double effect absorption refrigeration systems: Thermodynamic analysis
    Farshi, L. Garousi
    Asadi, S.
    [J]. APPLIED THERMAL ENGINEERING, 2018, 138 : 374 - 385
  • [9] A comparative study of the performance characteristics of double-effect absorption refrigeration systems
    Farshi, L. Garousi
    Mahmoudi, S. M. Seyed
    Rosen, M. A.
    Yari, M.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2012, 36 (02) : 182 - 192
  • [10] Second law analysis of double effect vapour absorption cooler system
    Gomri, Rabah
    Hakimi, Riad
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (11) : 3343 - 3348