Cooling energy savings and occupant feedback in a two year retrofit evaluation of 99 automated ceiling fans staged with air conditioning

被引:20
作者
Miller, Dana [1 ]
Raftery, Paul [1 ]
Nakajima, Mia [1 ]
Salo, Sonja [1 ,4 ]
Graham, Lindsay T. [1 ]
Peffer, Therese [1 ]
Delgado, Marta [1 ]
Zhang, Hui [1 ]
Brager, Gail [1 ]
Douglass-Jaimes, David [2 ]
Paliaga, Gwelen [2 ]
Cohn, Sebastian [3 ]
Greene, Mitch [3 ]
Brooks, Andy [3 ]
机构
[1] Univ Calif Berkeley, Ctr Built Environm, 390 Wurster Hall, Berkeley, CA 94720 USA
[2] TRC Co, 436 14th St Suite 1020, Oakland, CA 94612 USA
[3] Assoc Energy Affordabil AEA, 5900 Hollis St, Emeryville, CA 94608 USA
[4] Aalto Univ, Sch Engn, Otakaari 1, Aalto 00076, Finland
基金
美国国家科学基金会;
关键词
Air movement; Retrofit; Cooling; Energy efficiency; Thermal comfort; HVAC controls; THERMAL COMFORT; OFFICE; MOVEMENT; QUALITY; SPEEDS; WARM;
D O I
10.1016/j.enbuild.2021.111319
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Controlled air movement is an effective strategy for maintaining occupant comfort while reducing energy consumption, since comfort at moderately warmer temperatures requires less space cooling. Modern ceiling fans provide a 2-4 degrees C cooling effect at power consumption comparable to LED lightbulbs (2- 30 W) with gentle air speeds (0.5-1 m/s). However, very limited design guidance and performance data are available for using ceiling fans and air conditioning together, especially in commercial buildings. We present results from a 29-month field study of 99 automated ceiling fans and 12 thermostats installed in ten air-conditioned buildings in a hot/dry climate in California. Staging ceiling fans to automatically cool before, and then operate together with air conditioning enabled raising air conditioning cooling temper-ature setpoints in most zones, with overall positive occupant interview and survey responses. Overall measured cooling season (April- October) compressor energy savings were 36%, normalized by floor area served (41% during summer peak billing hours). Weather-normalized changes in zone energy use varied from 24% increase to 73% decrease across 13 compressors, reflecting variation in occupant schedules and other uncontrolled factors in occupied buildings. Median weather-normalized energy savings per com-pressor were 21%. Staging ceiling fans and air conditioning provided comfort across a wider temperature range, using less energy, than air conditioning alone. (c) 2021 The Author(s). Published by Elsevier B.V. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
引用
收藏
页数:16
相关论文
共 68 条
[1]  
Aerotron Fans, 2019, AER
[2]  
Allaire J., 2017, J STAT SOFTW
[3]  
Allaire J., 2018, rmarkdown: Dynamic Documents for R
[4]   Hamilton - A Cost-Effective, Low Power Networked Sensor for Indoor Environment Monitoring [J].
Andersen, Michael P. ;
Kim, Hyung-Sin ;
Culler, David E. .
BUILDSYS'17: PROCEEDINGS OF THE 4TH ACM INTERNATIONAL CONFERENCE ON SYSTEMS FOR ENERGY-EFFICIENT BUILT ENVIRONMENTS, 2017,
[5]  
[Anonymous], 2012, Commercial Buildings Energy Consumption Survey
[6]  
[Anonymous], 2015, Dynamic documents with R and knitr, DOI DOI 10.1201/9781315382487
[7]  
[Anonymous], 2016, SINBERBEST TECHNOLOG
[8]  
[Anonymous], 2020, ANSI/ASHRAE Standard 116-2012
[9]  
[Anonymous], 2007, 152512007 EN EUR COM
[10]  
[Anonymous], 2015, Guide to Determining Climate Regions by County