Thermal control of a mechanically pumped two-phase loop

被引:11
|
作者
Li, Guanru [1 ]
Jiang, Haitao [2 ]
Zheng, Yi [1 ]
Zhang, Chengbin [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Key Lab Energy Thermal Convers & Control, Minist Educ, Nanjing 210096, Peoples R China
[2] 38th Res Inst China Elect Technol Corp, Hefei 230088, Peoples R China
基金
国家重点研发计划;
关键词
Minichannel evaporator; Two-phase loop; Temperature control; Feed-forward compensation; Model predictive control; CAPILLARY-DRIVEN; FLOW-CONTROL; HEAT-PIPE; PERFORMANCE; THERMOSIPHON;
D O I
10.1016/j.icheatmasstransfer.2022.106365
中图分类号
O414.1 [热力学];
学科分类号
摘要
With integration and miniaturization of electronic devices, the heat dissipation has grown exponentially, necessitating feasible thermal management systems and cooling alternatives. Among them, two-phase loop cooling is deemed to be highly effective, in which the minichannel evaporator is rendered as a mechanically pumped two-phase loop (MPTL), ensuring the precise thermal control. Herein, the temperature control accuracy of MPTL has been particularly emphasized by proposing the feed-forward offset-free model predictive controller (MPC), and compared with the PI controller that has also been structurally modified (namely, improved PI controller). MPC is designed, optimized and tuned based on the unsteady-state nonlinear analysis, addressing the challenges, such as frequent heat load fluctuations and various nonlinearities/uncertainties mainly encountered during the minichannel boiling. Results depict the superiority of MPC in terms of shorter transient time (measured by set-point tracking), higher temperature control accuracy and lower absolute error (IAE) index (both determined by disturbance rejection), mitigating the effect of flow-boiling uncertainties. Especially, the average transient time of MPC on MPTL has been found at least four times shorter than that of the improved PI controller. Also, IAE index of MPC on MPTL is better than that of the improved PI controller. Meanwhile, the temperature control accuracy of MPC on MPTL during disturbance suppression is as little as 0.2 degrees C, while that of the improved PI is higher (1.1 degrees C). The temperature control of the proposed controller (MPC) is therefore satisfactory based on which it can be engaged in MPTL technology for further development of electronic applications.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Experimental study on active disturbance rejection temperature control of a mechanically pumped two-phase loop
    Zhang, Chengbin
    Li, Guanru
    Sun, Li
    Chen, Yongping
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 129 : 1 - 10
  • [2] Extended state observer-based model predictive temperature control of mechanically pumped two-phase loop: An experimental study
    Li, Guanru
    Madonski, Rafal
    Lakomy, Krzysztof
    Sun, Li
    Lee, Kwang Y.
    APPLIED THERMAL ENGINEERING, 2022, 213
  • [3] Ground Test and on-Orbit Verification of a Mechanically Pumped Two-Phase Loop Using for Thermal Control of Spacecraft
    Meng, Qingliang
    Zhao, Zhenming
    Chen, Xianggui
    HEAT TRANSFER ENGINEERING, 2023, 44 (16-18) : 1624 - 1642
  • [4] Experimental study on the transient behaviors of mechanically pumped two-phase loop with a novel accumulator for thermal control of space camera payload
    Meng, Qingliang
    Zhao, Zhenming
    Zhang, Tao
    van Es, Johannes
    Pauw, Aswin
    Zhang, Huandong
    Yan, Yinxue
    APPLIED THERMAL ENGINEERING, 2020, 179
  • [5] Thermodynamic modeling and optimization of hybrid linear concentrating photovoltaic and mechanically pumped two-phase loop system
    Li, Guanru
    Hua, Qingsong
    Sun, Li
    Khosravi, Ali
    Pabon, Juan Jose Garcia
    APPLIED ENERGY, 2023, 333
  • [6] Numerical Simulations and Analyses of Mechanically Pumped Two-Phase Loop System for Space Remote Sensor
    Yu, Feng
    Meng, Qingliang
    ENERGIES, 2022, 15 (14)
  • [7] Experimental Study on the Dynamic Heat Transfer Characteristics of a Mechanically Pumped Two-phase Cooling Loop
    Li, Lei
    Tao, Jianyun
    Gao, Wei
    FRONTIERS IN ENERGY RESEARCH, 2021, 9 (09):
  • [8] Dynamic thermal response behaviors of pumped two-phase loop with latent heat storage
    Zhang, Chengbin
    Zhang, Yingjuan
    Sheng, Jiang
    Li, Bo
    Chen, Yongping
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2024, 225
  • [9] Experimental study on dynamic behavior of mechanically pumped two-phase loop with a novel accumulator in simulated space environment
    Meng, Qingliang
    Zhang, Tao
    Yu, Feng
    Zhao, Yu
    Zhao, Zhenming
    Zhou, Zhenhua
    CHINESE JOURNAL OF AERONAUTICS, 2022, 35 (12) : 102 - 116
  • [10] Study on the flow boiling characteristics of novel pin fin heat sinks in a two-phase mechanically pumped cooling loop
    Wang, Jiale
    Qi, Shaohuan
    Xu, Zhaohao
    Xu, Yu
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 60