Combined effects of subcooling and surface orientation on pool boiling of HFE-7100 from a simulated electronic chip

被引:47
作者
El-Genk, MS [1 ]
Bostanci, H
机构
[1] Univ New Mexico, Inst Space & Nucl Power Studies, Albuquerque, NM 87131 USA
[2] Univ New Mexico, Dept Chem & Nucl Engn, Albuquerque, NM 87131 USA
关键词
D O I
10.1080/08916150390242244
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effects of orientation and subcooling on pool boiling of the HFE-7100 dielectric liquid near atmospheric pressure (0.085 MPa) from a 10 x 10 mm smooth copper surface are investigated experimentally. Results are obtained for inclination angles theta = 0degrees (upward-facing), 30degrees, 60degrees, 90degrees, 120degrees, 150degrees, and 180degrees (downward-facing) and liquid subcoolings DeltaT(sub) = 0, 10, 20, and 30 K. Increasing theta decreases the saturation nucleate boiling heat flux at high surface superheats (DeltaT(sat) > 20 K), but increases it only slightly at lower surface superheats. The critical heat flux (CHF) decreases slowly with increasing theta from 0degrees to 90degrees, and then deceases faster with increasing theta to 180degrees. CHF increases linearly with increased subcooling, but the rate increases from 0.016 K -1 at 0degrees to 0.048 K -1 at 180degrees. At theta = 0degrees and DeltaT(sub) = 30 K, CHF is similar to 36 W/cm(2) and 24.45 W/cm(2) for saturation boiling, while at theta = 180degrees CHF = 10.85 W/cm 2 at DeltaT(sub) = 30 K and only 4.30 W/cm(2) at saturation. The developed correlation for CHF of HFE-7100, as a function of theta and DeltaT(sub) , is within +/-10% of the present data. The recorded still photographs of the boiling surface in the experiments illustrate the effects of liquid subcooling and surface orientation at different nucleate boiling heat fluxes and surface superheats on vapor bubble accumulation and/or induced mixing at the surface.
引用
收藏
页码:281 / 301
页数:21
相关论文
共 19 条
[1]  
Arik M., 2001, P PAC RIM INT INT EL, P18
[2]  
CARVALHO RD, 1990, P 9 INT HEAT TRANSF, V2, P289
[3]   Heater orientation effects on pool boiling of micro-porous-enhanced surfaces in saturated FC-72 [J].
Chang, JY ;
You, SM .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1996, 118 (04) :937-943
[4]  
CHANG Y, 1997, ADV ELECT PACKAGING, V19, P2055
[5]   Saturation boiling of HFE-7100 from a copper surface, simulating a microelectronic chip [J].
El-Genk, MS ;
Bostanci, H .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2003, 46 (10) :1841-1854
[6]  
ELGENK MS, 1993, INT J REFRIG, V6, P414
[7]  
HWANG UP, 1981, HEAT TRANSFER ELECTR, V20, P53
[8]  
IVEY H, 1962, AEEWR137 UK AT EN AU
[9]  
Kutateladze S.S., 1961, INT J HEAT MASS TRAN, V4, P31, DOI [10.1016/0017-9310, DOI 10.1016/0017-9310]
[10]  
Lee T.Y.T., 1992, ASME HTD, V206, P55