Comparative study of a novel liquid-vapour separator incorporated gravitational loop heat pipe against the conventional gravitational straight and loop heat pipes - Part II: Experimental testing and simulation model validation

被引:9
作者
Zhang, Xingxing [1 ,2 ]
Shen, Jingchun [2 ]
He, Wei [2 ,3 ]
Xu, Peng [2 ,4 ]
Zhao, Xudong [2 ]
Tan, Junyi [5 ]
机构
[1] Univ Nottingham, Dept Architecture & Built Environm, Ningbo, Zhejiang, Peoples R China
[2] Univ Hull, Sch Engn, Kingston Upon Hull HU6 7RX, N Humberside, England
[3] Univ Sci & Technol China, Dept Thermal Sci & Energy Engn, Hefei, Anhui, Peoples R China
[4] Beijing Univ Civil Engn & Architecture, Sch Environm & Energy Engn, Beijing, Peoples R China
[5] Zhuhai Singyes Renewable Energy Technol Co Ltd, Zhuhai, Guangdong, Peoples R China
关键词
Heat pipe; Start up; Thermal conductivity; Experiment; Model validation; PERFORMANCE; SYSTEM;
D O I
10.1016/j.enconman.2015.01.035
中图分类号
O414.1 [热力学];
学科分类号
摘要
Aim of the paper is to report the experimental study of a novel liquid-vapour separator incorporated gravity-assisted loop heat pipe (GALHP) (T1), against the conventional GALHP (T2) and a gravitational straight heat pipe (13). Based on the results derived from the theoretical analyses and computer modelling, three prototype heat pipes, one for each type, were designed, constructed and tested to characterise their thermal performance under a series of operational conditions. By using the experimental data, the computer simulation model reported in the authors' previous paper was examined and analysed, indicating that the model could achieve a reasonable accuracy in predicting the thermal performance of the three heat pipes. Under the specifically defined testing condition, T1 has more evenly distributed axial. temperature profile than the other two heat pipes (12 and T3). The start-up timings for 11, 12 and T3 were 410s, 1400 s and 390 s respectively, indicating that the heat transfer within 12 was affected by the larger evaporator dry-out surface area and restricted evaporation area. The overall thermal resistance of 11 was 0.11 degrees C/W, which was around 20% and 50% that of 12 and T3. The tested effective thermal conductivity in T1 was 29,968 W/degrees C in, which was 296% and 648% that of 12 and T3, and 7492% that of a standard copper rod. It is therefore concluded that the novel heat pipe (T1) could achieve a significantly enhanced heat transport effect, relative to 12, 13 and standard cooper rod. The experimental results derived from this research enabled characterisation of the thermal performance of T1, relative to other heat pipes, and validation of the developed computer simulation model derived from the authors' previous research. These two parts researches in combination will enable design, optimisation and analyse of such a new GALHP, thus promoting its wide application and achieving efficient thermal management. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:228 / 238
页数:11
相关论文
共 20 条
  • [1] Evaluating the possible configurations of incorporating the loop heat pipe into the air-conditioning systems
    Alklaibi, A. M.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (05): : 807 - 815
  • [2] Amir Faghri, 1995, HEAT PIPE SCIENCE AN
  • [3] [Anonymous], HEAT PIPES THEORY DE
  • [4] Numerical investigation on effect of riser diameter and inclination on system parameters in a two-phase closed loop thermosyphon solar water heater
    Aung, Nay Zar
    Li, Songjing
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2013, 75 : 25 - 35
  • [5] Copper-water loop heat pipes for energy-efficient cooling systems of supercomputers
    Chernysheva, M. A.
    Yushakova, S. I.
    Maydanik, Yu. F.
    [J]. ENERGY, 2014, 69 : 534 - 542
  • [6] Concepts of self-acting circulation loops for downward heat transfer (reverse thermosiphons)
    Dobriansky, Y.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (01) : 414 - 425
  • [7] Theoretical investigation of the thermal performance of a novel solar loop-heat-pipe facade-based heat pump water heating system
    He, Wei
    Hong, Xiaoqiang
    Zhao, Xudong
    Zhang, Xingxing
    Shen, Jinchun
    Ji, Jie
    [J]. ENERGY AND BUILDINGS, 2014, 77 : 180 - 191
  • [8] JCGM, 2008, EVALUATION OF MEASUR
  • [9] Experimental investigation of wraparound loop heat pipe heat exchanger used in energy efficient air handling units
    Jouhara, Hussam
    Meskimmon, Richard
    [J]. ENERGY, 2010, 35 (12) : 4592 - 4599
  • [10] A loop-heat-pipe heat sink with parallel condensers for high-power integrated LED chips
    Li, Ji
    Lin, Feng
    Wang, Daming
    Tian, Wenkai
    [J]. APPLIED THERMAL ENGINEERING, 2013, 56 (1-2) : 18 - 26