Improvement of VSG Transient Performance Based on Power Feedforward Decoupling Control

被引:10
作者
Liu, Andong [1 ]
Liu, Jun [1 ]
Wu, Qiong [1 ]
机构
[1] Xian Univ Technol, Coll Automat, 5 Jinhua South Rd, Xian, Peoples R China
关键词
frequency fluctuation; power feedforward decoupling control (PFDC); small signal analysis; synchronous frequency resonance (SFR); virtual synchronous generator (VSG); VIRTUAL SYNCHRONOUS GENERATORS;
D O I
10.1049/gtd2.12574
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The suppression of power grid frequency fluctuation, the inhibition of output active power oscillation, and the coupling of active and reactive power at the output of the virtual synchronous generator (VSG) are all investigated in this work. The connection between VSG output active power oscillation inhibition and grid frequency fluctuation suppression is explored, as well as the difficulties of achieving both power oscillation suppression and frequency fluctuation suppression for VSG at the same time. To overcome this problem, a control approach incorporating notch filter power feedforward decoupling and modifying virtual damping coefficient is presented, it is called power feedforward decoupling control (PFDC). The virtual resistance will worsen the P/Q coupling, whereas the virtual inductance will have no effect, according to the results of the P/Q coupling analysis. It can be demonstrated that the suggested solution does not jeopardize P/Q decoupling performance for VSG active power oscillation suppression and grid frequency fluctuation suppression. The understanding of VSG transient performance is deepened by the comprehensive investigation of the three issues. Finally, simulation is used to verify the soundness of the theoretical analysis and proposed strategy, while VSG's transient performance is increased even more.
引用
收藏
页码:4080 / 4095
页数:16
相关论文
共 23 条
[1]   Stability Assessment and Optimization Methods for Microgrid With Multiple VSG Units [J].
Alipoor, Jaber ;
Miura, Yushi ;
Ise, Toshifumi .
IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (02) :1462-1471
[2]   Power System Stabilization Using Virtual Synchronous Generator With Alternating Moment of Inertia [J].
Alipoor, Jaber ;
Miura, Yushi ;
Ise, Toshifumi .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2015, 3 (02) :451-458
[3]  
Baltas Gregory N., 2021, IEEE ACCESS, V311, P2070
[4]  
Choopani M., 2020, IEEE T POWER SYSTEMS, V35
[5]   Active Power Sharing and Frequency Restoration in an Autonomous Networked Microgrid [J].
Eskandari, Mohsen ;
Li, Li ;
Moradi, Mohammad Hassan ;
Siano, Pierluigi ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) :4706-4717
[6]   Analysis of Resonance in Microgrids and Effects of System Frequency Stabilization Using a Virtual Synchronous Generator [J].
Hirase, Yuko ;
Sugimoto, Kazushige ;
Sakimoto, Kenichi ;
Ise, Toshifumi .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2016, 4 (04) :1287-1298
[7]  
Hu Y., 2020, IEEE J EM SEL TOP P, V8
[8]  
Lai N.B., 2021, IEEE T IND APPL
[9]   Improved power decoupling control strategy based on virtual synchronous generator [J].
Li, Bin ;
Zhou, Lin ;
Yu, Xirui ;
Zheng, Chen ;
Liu, Jinhong .
IET POWER ELECTRONICS, 2017, 10 (04) :462-470
[10]  
Li D., 2017, IEEE T ENERGY CONVER, V32