A dynamic model for predicting condensation heat and mass transfer characteristics in falling film condenser

被引:7
作者
Jiang, Jiatong [1 ,2 ]
Hu, Bin [1 ,2 ]
Wang, R. Z. [1 ,2 ]
Liu, Hua [1 ,2 ,3 ]
Zhang, Zhiping [3 ]
Li, Hongbo [3 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
[2] Shanghai Jiao Tong Univ, Engn Res Ctr Solar Power & Refrigerat, Shanghai 200240, Peoples R China
[3] GREE Elect Appliances INC, SKL Air Conditioning Equipment & Syst Energy Cons, Zhuhai 519070, Peoples R China
基金
中国国家自然科学基金;
关键词
Falling film simulation; Dynamic condensation model; Vapor-mass-flux ratio; Enhanced heat transfer; R1233zd(E); PERFORMANCE;
D O I
10.1016/j.ijheatmasstransfer.2021.121434
中图分类号
O414.1 [热力学];
学科分类号
摘要
A mathematical model of falling film condenser is developed to predict the dynamic response of shelland-tube condenser having R1233zd(E) as refrigerant for high temperature heat pump systems. The model incorporates a vapor-mass-flux ratio, which includes the relative velocity slip between vapor and liquid to examine the performance of tube bundles in falling film condensers. Discretization of governing equations and control-volumes method are applied to construct the dynamic model which is first validated with the well-known HTRI software in steady-state performance. The mean relative deviations are within 14.8% for temperature and 2.0% for heating capacity in steady state. The established model can be used to predict the dynamic heat transfer response to the change of operating conditions and geometric configurations of tubing. When compared to the change of inlet pressure of vapor refrigerant, the response of the condensation temperature is much slower, yielding some 1.7 times longer time to reach stable state than that of pressure. Further, various heat exchange tubes (smooth tubes and low-fin tubes with 3 different fin pitches) are examined. It is found that the heating capacity and water outlet temperature increase with the rise of fin density. Yet higher fin density also tends to reach stable state earlier. The heat transfer enhancement ratio ranges from 2.7 to 2.0 for low-fin tube with 1.3 mm fin pitch, and the enhanced tubes are more effective with the low subcooling temperature. (C) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:11
相关论文
共 24 条
[1]  
Battisti R., 2020, CHEM ENG PROCESS PRO, V150, P31
[2]   Comprehensive review of pure vapour condensation outside of horizontal smooth tubes [J].
Bonneau, Clement ;
Josset, Christophe ;
Melot, Vincent ;
Auvity, Bruno .
NUCLEAR ENGINEERING AND DESIGN, 2019, 349 :92-108
[3]   Modelling of heat and mass transfer in a horizontal-tube falling-film condenser for brackish water desalination in remote areas [J].
Bourouni, K ;
Chaibi, MT .
DESALINATION, 2004, 166 (1-3) :17-24
[4]  
Butterworth D., 1983, Heat Exchanger Design Handbook, V2, P10
[5]  
Calle A., 2015, MODELLING SIMULATION
[6]   Extension of the applicable range of the implicit curve-fitting method for refrigerant thermodynamic properties to critical pressure [J].
Ding, Guo Liang ;
Wu, Zhigang ;
Wang, Kaijian ;
Fukaya, Masaharu .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (03) :418-432
[7]  
Eissenberg D.M., 1970, COMPUTER MODEL CORRE
[8]   Refrigerant falling film evaporation review: Description, fluid dynamics and heat transfer [J].
Fernandez-Seara, Jose ;
Pardinas, Angel A. .
APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) :155-171
[9]  
Grant I.D.R., 1968, Technical Report 350
[10]  
Gu B., 2001, J REFRIGERATION CHIN, P6