Finite-difference prediction of transient indoor temperature and related correlation based on the building time constant

被引:0
作者
Antonopoulos, KA
Tzivanidis, C
机构
[1] Natl. Technical University of Athens, Mechanical Engineering Department, Thermal Section, Athens 106 82
关键词
indoor temperature; building time constant; building thermal response;
D O I
10.1002/(SICI)1099-114X(199606)20:6<507::AID-ER167>3.0.CO;2-T
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A numerical procedure for the calculation of the transient indoor temperature in buildings is developed. The procedure is based on an implicit finite-difference solution of a closed set of differential equations, which express the indoor energy balance and the transient heat conduction in all elements of the building envelope. Using the above procedure, calculations are carried out for 21 types of buildings with 18 and 10 different kinds of wall and roof constructions, respectively, i.e. the total number of building cases examined is 21 x 18 x 10 = 3780 with floor areas ranging from 30 m(2) to 3000 m(2). It is found that buildings of different construction characteristics and sizes but with the same time constant, respond in a similar way under the same outdoor temperature variation. Based on this similarity, a correlation is developed which expresses, under periodic conditions, the indoor temperature variation in terms of the building time constant and the outdoor temperature characteristics. The correlation contains nine coefficients, the values of which are different for different ranges of the building time constant.
引用
收藏
页码:507 / 520
页数:14
相关论文
共 7 条
[1]   EFFECTS OF INDOOR AND OUTDOOR HEAT-TRANSFER COEFFICIENTS AND SOLAR ABSORPTANCE ON HEAT-FLOW THROUGH WALLS [J].
ANTONOPOULOS, KA ;
VALSAMAKIS, SP .
ENERGY, 1993, 18 (03) :259-271
[2]   TIME CONSTANT OF GREEK BUILDINGS [J].
ANTONOPOULOS, KA ;
TZIVANIDIS, C .
ENERGY, 1995, 20 (08) :785-802
[3]  
ASHRAE, 1993, ASHRAE FUND
[4]  
BUCHBERG H., 1969, BUILDING SCI, V4, P43
[5]  
Pantankar S.V., 1980, Numerical Heat Transfer and Fluid Flow, V1
[6]   SHAVING RESIDENTIAL AIR-CONDITIONER ELECTRICITY PEAKS BY INTELLIGENT USE OF THE BUILDING THERMAL MASS [J].
REDDY, TA ;
NORFORD, LK ;
KEMPTON, W .
ENERGY, 1991, 16 (07) :1001-1010
[7]  
Stephenson D.G., 1967, ASHRAE T, V73