Upstream impedance diagnostic for three-phase induction motors

被引:0
作者
Bockstette, Jens [1 ]
Stolz, Erik [2 ]
Wiedenbruig, Ernesto [2 ]
机构
[1] Rhein Westfal TH Aachen, Inst Power Elect & Elect Dr, Aachen, Germany
[2] Baker Instrument Co, Ft Collins, CO 80525 USA
来源
2007 IEEE INTERNATIONAL SYMPOSIUM ON DIAGNOSTICS FOR ELECTRIC MACHINES, POWER ELECTRONICS & DRIVES | 2007年
关键词
impedance; contact resistance; induction motors;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a simple method of diagnosing the upstream impedance of a three-phase induction motor by analyzing the across-the-line startup current and voltage time-waveforms. Thermography is currently the only industrial method capable of detecting upstream contact resistance problems, but it requires line of sight to the location of the problem. The proposed method does not have this drawback. The accuracy of the resistive unbalance threshold settings used with mu Omega-meters to diagnose downhill contact resistance issues in industrial settings was exceeded with the proposed methods in a laboratory implementation.
引用
收藏
页码:30 / +
页数:2
相关论文
共 12 条
  • [1] ARRILLAGA J, 2004, POWER SYSTEM HARMONI, P196
  • [2] *BAK INSTR COMP, 2007, ADV WIND AN 4 US MAN, P62
  • [3] COMO D, 2007, PLANT SERVICES
  • [4] *EPRI, 1992, NP7502281435 EPRI, P3
  • [5] *EPRI, 2000, 1000968 EPRI, pB19
  • [6] MOHAN N, 1995, POWER ELECT, P435
  • [7] *NEMA, 2006, NEMA STAND PUBL MG, V1
  • [8] *NEMA, 1994, NEMA STAND PUBL MG, V10
  • [9] SCHLABBACH J, 2001, IEE POWER ENERGY SER, V36, P147
  • [10] Assessment of voltage unbalance
    von Jouanne, A
    Banerjee, B
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) : 782 - 790