Sequence-Based Control Strategy With Current Limiting for the Fault Ride-Through of Inverter-Interfaced Distributed Generators

被引:116
作者
Mahamedi, Behnam [1 ]
Eskandari, Mohsen [1 ]
Fletcher, John E. [2 ]
Zhu, Jianguo [3 ]
机构
[1] Univ Technol Sydney, Sch Elect & Data Engn, Sydney, NSW 2007, Australia
[2] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW 2052, Australia
[3] Univ Sydney, Sch Elect & Informat Engn, Sydney, NSW 2006, Australia
关键词
Inverters; Limiting; Power quality; Voltage control; Current limiters; Power system stability; Delays; Current limiting; fault ride-through (FRT); inverter-interfaced distributed generator (IIDG); magnitude calculator; sequence-based control; synchronous reference frame (SYRF); PEAK CURRENT LIMITATION; POWER ELECTRONICS; CONVERTER; IMPEDANCE; SCHEME;
D O I
10.1109/TSTE.2018.2887149
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Three-phase three-leg inverters represent the majority of inverters that are integrated into low voltage power grids. They can develop positive- and negative-sequence components during unbalanced conditions including asymmetrical faults, but not zero-sequence components. This indicates that a sequence-based control strategy is required for comprehensive control of inverter currents and voltages. Positive- and negative-sequence components must be controlled separately with their own dedicated controllers in such a scheme. Given this critical need, a sequence-based control technique for grid-forming and grid-feeding inverter-interfaced distributed generators is proposed. As a necessary part of the fault ride-through capability of inverter-interfaced distributed generators, a current limiter is developed, which can limit inverter currents at a pre-defined threshold for both balanced and unbalanced faults. Whilst the current regulators work in the synchronous reference frame with simple PI controllers, the limiter works in the natural reference frame and thus treats each phase current separately, which results in current limiting at the threshold for all phases. The advantage of the proposed limiter is that it acts instantaneously such that the inverter current can be limited from the start of the disturbance. The simulation results in MATLAB/SIMULINK reveal promising performance of the proposed control strategy with the proposed current limiting.
引用
收藏
页码:165 / 174
页数:10
相关论文
共 36 条
[21]   DIGITAL CALCULATION OF IMPEDANCE FOR TRANSMISSION LINE PROTECTION [J].
MANN, BJ ;
MORRISON, IF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (01) :270-&
[22]   New Voltage Control Strategies for VSC-Based DG Units in an Unbalanced Microgrid [J].
Merritt, Noel Richard ;
Chakraborty, Chandan ;
Bajpai, Prabodh .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (03) :1127-1139
[23]   Power electronics cooling effectiveness versus thermal inertia [J].
Meysenc, L ;
Jylhäkallio, M ;
Barbosa, P .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (03) :687-693
[24]   Resonant Versus Conventional Controllers in Grid-Connected Photovoltaic Power Plants Under Unbalanced Grid Voltages [J].
Mirhosseini, Mitra ;
Pou, Josep ;
Karanayil, Baburaj ;
Agelidis, Vassilios G. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2016, 7 (03) :1124-1132
[25]   Single- and Two-Stage Inverter-Based Grid-Connected Photovoltaic Power Plants With Ride-Through Capability Under Grid Faults [J].
Mirhosseini, Mitra ;
Pou, Josep ;
Agelidis, Vassilios G. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2015, 6 (03) :1150-1159
[26]   Improving During and Postfault Response of Fuel Cells in Symmetrical and Asymmetrical Grid Fault Cases [J].
Mojallal, Aslan ;
Lotfifard, Saeed .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (03) :1407-1418
[27]   Peak Current Limitation for Grid Side Inverter by Limited Active Power in PMSG-Based Wind Turbines During Different Grid Faults [J].
Nasiri, Mojtaba ;
Mohammadi, Reza .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (01) :3-12
[28]   Short-Circuit Fault Protection Strategy for High-Power Three-Phase Three-Wire Inverter [J].
Pei, Xuejun ;
Kang, Yong .
IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2012, 8 (03) :545-553
[29]  
Plet C.A., 2012, Fault Response of Inverter -Based Distributed Generation
[30]   An Effective Reference Generation Scheme for DFIG With Unbalanced Grid Voltage [J].
Rani, M. A. Asha ;
Nagamani, C. ;
Ilango, G. Saravana ;
Karthikeyan, A. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2014, 5 (03) :1010-1018