Energy performance enhancement in air-source heat pump with a direct evaporative cooler-applied condenser

被引:14
作者
Kim, Beom-Jun [1 ]
Jo, Su-Young [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Coll Engn, Dept Architectural Engn, Seoul 04763, South Korea
关键词
Air-source heat pump; Direct evaporative cooler; Optimal system operation; Outdoor air condition; Energy-saving potential; SYSTEM; SIMULATION; CONDITIONER;
D O I
10.1016/j.csite.2022.102137
中图分类号
O414.1 [热力学];
学科分类号
摘要
The energy consumption of the air-source heat pump operated in cooling mode is affected by the outdoor air condition in summer. It is important to not only install the evaporative cooler in front of the condenser inlet side but also consider the operation strategy of the evaporative cooler under the hot and humid condition. In this study, the energy saving potential of the air-source heat pump with an evaporative cooler was analyzed according to the operation strategy. A three-story office building measuring 100 m(2), using an enthalpy recovery ventilator, was used as a model building conditioned by the proposed system for detailed energy simulation. The building thermal load and energy consumption were estimated using simulation tools. The results show that the proposed system reduces 8.87% of energy consumption compared with the conventional air-source heat pump when the evaporative cooler operated under the 72% of relative humidity condition.
引用
收藏
页数:17
相关论文
共 37 条
  • [1] [Anonymous], MUNTERS EVAPORATIVE
  • [2] [Anonymous], 2020, ANSI/ASHRAE Standard 55-2020 Thermal Environmental Conditions for Human Occupancy
  • [3] [Anonymous], 2019, 6212019 ASHRAE
  • [4] ASHRAE, 2019, ANSI/ASHRAE/IES Standard 90.1-2019
  • [5] Modelling and simulation of a heat pump for simultaneous heating and cooling
    Byrne, Paul
    Miriel, Jacques
    Lenat, Yves
    [J]. BUILDING SIMULATION, 2012, 5 (03) : 219 - 232
  • [6] Camargo J.R., 2003, ENGENHARIA TERMICA, V4, P30, DOI [10.5380/reterm.v2i2.3473, DOI 10.5380/RETERM.V2I2.3473]
  • [7] Direct evaporative passive cooling of building. A comparison amid simplified simulation models based on experimental data
    Chiesa, Giacomo
    Grosso, Mario
    [J]. BUILDING AND ENVIRONMENT, 2015, 94 : 263 - 272
  • [8] Advances in heat pump systems: A review
    Chua, K. J.
    Chou, S. K.
    Yang, W. M.
    [J]. APPLIED ENERGY, 2010, 87 (12) : 3611 - 3624
  • [9] Simulation study of a heat pump for simultaneous heating and cooling coupled to buildings
    Ghoubali, Redouane
    Byrne, Paul
    Miriel, Jacques
    Bazantay, Frederic
    [J]. ENERGY AND BUILDINGS, 2014, 72 : 141 - 149
  • [10] Givoni B., 1994, PASSIVE LOW ENERGY C