An Influence of Air Volume Flow Rate and Temperature Set Point on Performance of Inverter Split-Type Air-Conditioner

被引:1
|
作者
Rachapradit, N. [1 ]
Thepa, S. [1 ]
Monyakulb, V. [2 ]
机构
[1] King Mongkuts Univ Technol Thonburi KMUTT, Sch Energy Environm & Mat, Bangkok 10140, Thailand
[2] Natl Sci & Technol Dev Agcy NSTDA, Pathum Thani, Thailand
关键词
Air-Conditioner; Air Volume Flow Rate; Energy Saving; Inverter; HUMIDITY CONTROL; A/C UNIT; CAPACITY CONTROLLER; COMPRESSOR; THAILAND; HOT;
D O I
10.1111/j.1747-1567.2011.00720.x
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
This paper presents an experimental and analytical study on the inverter split-type air-conditioner for the purpose of energy saving and a proper balance between sensible and latent capacity. Performance of an inverter split-type air-conditioner is investigated at varied refrigerant mass flow rates, air volume flow rates, and set point temperatures. The performance investigated for a 2.54-kW inverter split-type air-conditioner includes cooling capacity, power consumption, the value of coefficient of performance (COP), and equipment sensible heat ratio (SHR). An increase of electrical frequency input to compressor from 34 to 66 Hz results in an increase of cooling capacity by 0.88 kW, a decrease of COP by 0.84, and a decrease of SHR by 0.11. An increase in cooling coil flow rate from 4.14 to 8.2 m3/min results in an increase in cooling capacity by 0.16 kW, an increase in COP by 0.10, and an increase in SHR by 0.15. An increase of set point temperature from 24 to 26 degrees C results in an increase of the value of COP by 0.13 and a decrease of SHR by 0.03. The study offers guidelines for the application of small-size inverter split-type air-conditioners in hot and humid climates.
引用
收藏
页码:18 / 25
页数:8
相关论文
共 50 条
  • [1] An influence of air volume flow rate and temperature set point on performance of inverter split-type air-conditioner
    N. Rachapradit
    S. Thepa
    V. Monyakulb
    Experimental Techniques, 2012, 36 : 18 - 25
  • [2] On similitude of the cross flow fan in a split-type air-conditioner
    Shih, Yang-Cheng
    Hou, Hung-Chi
    Chiang, Hsucheng
    APPLIED THERMAL ENGINEERING, 2008, 28 (14-15) : 1853 - 1864
  • [3] Prediction and measurement of axial flow fan aerodynamic and aeroacoustic performance in a split-type air-conditioner outdoor unit
    Zhao, Xifeng
    Sun, Jinju
    Zhang, Zhi
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (03): : 1098 - 1108
  • [4] Performance Monitoring and Prediction of a Domestic Split-type Air Conditioner
    Bantan, Glory M.
    Tangwe, Stephen L.
    Simon, M.
    PROCEEDINGS OF THE 2017 TWENTY FIFTH INTERNATIONAL CONFERENCE ON THE DOMESTIC USE OF ENERGY (DUE), 2017, : 220 - 226
  • [5] Effect of condensing unit layout at building re-entrant on split-type air-conditioner performance
    Chow, TT
    Lin, Z
    Liu, JP
    ENERGY AND BUILDINGS, 2002, 34 (03) : 237 - 244
  • [6] Experimental study on the effect of the split-type air-conditioner on the transmission of smoking pollutants in a room
    Xie, Ruoyi
    Xu, Yiyang
    Chen, Guangming
    Zhang, Shaozhi
    JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 2022, 72 (10) : 1113 - 1120
  • [7] An empirical model of a split-type inverter air conditioner for building energy simulation
    Pizzatto, Leandro Reichembach
    Nascimento, Carlos A. Richter
    Mendes, Nathan
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [8] Thermohydraulic and condensing phase-change analysis within the indoor unit of a split-type air-conditioner
    Tsao, Chung-Chun
    Shih, Yang-Cheng
    Lin, Chun-Hsiung
    Chao, Ling-Yu
    Hu, Shih-Cheng
    CASE STUDIES IN THERMAL ENGINEERING, 2020, 21
  • [9] Investigation of air-flow fields and aeroacoustic noise in outdoor unit for split-type air conditioner
    Jiang, Cai-Ling
    Tian, Jie
    Ouyang, Hua
    Chen, Jiang-Ping
    Chen, Zhi-Jiu
    NOISE CONTROL ENGINEERING JOURNAL, 2006, 54 (03) : 146 - 156
  • [10] Empirical Correlations for Sizing Adiabatic Capillary Tube using LPG as Refrigerant in Split-Type Air-conditioner
    Sulaimon, Shodiya
    Abdulaziz, Azhar
    Darus, Amer N.
    Henry, Nasution
    ADVANCES IN APPLIED MECHANICS AND MATERIALS, 2014, 493 : 99 - 104