Transmission line parameter identification using PMU measurements

被引:77
|
作者
Shi, Di [1 ]
Tylavsky, Daniel J.
Koellner, Kristian M. [2 ]
Logic, Naim [2 ]
Wheeler, David E. [2 ]
机构
[1] Arizona State Univ, Dept Elect Engn, Sch Elect Comp & Energy Engn, Tempe, AZ 85287 USA
[2] Salt River Project, Phoenix, AZ 85072 USA
来源
关键词
PMU; GPS-synchronized phasor measurement; positive sequence transmission line model; transmission line impedance parameters; linear estimation theory;
D O I
10.1002/etep.522
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate knowledge of transmission line (TL) impedance parameters helps to improve accuracy in relay settings and power flow modeling. To improve TL parameter estimates, various algorithms have been proposed in the past to identify TL parameters based on measurements from Phasor Measurement Units (PMUs). These methods are based on the positive sequence TL models and can generate accurate positive sequence impedance parameters for a fully transposed TL when measurement noise is absent; however, these methods may generate erroneous parameters when the TLs are not fully transposed or when measurement noise is present. PMU field-measure data are often corrupted with noise and this noise is problematic for all parameter identification algorithms, particularly so when applied to short TLs. This paper analyzes the limitations of the positive sequence TL model when used for parameter estimation of TLs that are untransposed and proposes a novel method using linear estimation theory to identify TL parameters more reliably. This method can be used for the most general case: short/long lines that are fully transposed or untransposed and have balanced/unbalance loads. Besides the positive/negative sequence impedance parameters, the proposed method can also be used to estimate the zero sequence parameters and the mutual impedances between different sequences. This paper also examines the influence of noise in the PMU data on the calculation of TL parameters. Several case studies are conducted based on simulated data from ATP to validate the effectiveness of the new method. Through comparison of the results generated by this novel method and several other methods, the effectiveness of the proposed approach is demonstrated. Copyright (C) 2010 John Wiley & Sons, Ltd.
引用
收藏
页码:1574 / 1588
页数:15
相关论文
共 50 条
  • [1] Identification and Estimation of Erroneous Transmission Line Parameters Using PMU Measurements
    Asprou, Markos
    Kyriakides, Elias
    IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) : 2510 - 2519
  • [2] Identification and Estimation of Erroneous Transmission Line Parameters Using PMU Measurements
    Asprou, Markos
    Kyriakides, Elias
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [3] On-Line PMU-Based Transmission Line Parameter Identification
    Zhao, Xuanyu
    Zhou, Huafeng
    Shi, Di
    Zhao, Huashi
    Jing, Chaoyang
    Jones, Chris
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2015, 1 (02): : 68 - 74
  • [4] Estimation of Transmission Line Parameters Using PMU Measurements
    Asprou, Markos
    Kyriakides, Elias
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [5] Transmission line parameter identification method based on PMU error correction
    Zhang J.
    Lei J.
    He Y.
    Wu P.
    Yu J.
    Xiang M.
    Ren P.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (19): : 130 - 137
  • [6] Double Circuit Transmission Line Parameter Estimation Using PMU
    Unde, Snehal V.
    Dambhare, Sanjay S.
    2016 IEEE 6TH INTERNATIONAL CONFERENCE ON POWER SYSTEMS (ICPS), 2016,
  • [7] Calculating Sequence Impedances of Transmission Line Using PMU Measurements
    Zhou Huafeng
    Zhao Xuanyu
    Shi Di
    Zhao Huashi
    Jing Chaoyang
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [8] On-line Overhead Transmission Line And Transformer Parameters Identification Based On PMU Measurements
    Vicol, Bogdan
    2014 INTERNATIONAL CONFERENCE AND EXPOSITION ON ELECTRICAL AND POWER ENGINEERING (EPE), 2014, : 1045 - 1050
  • [9] Identification and correction of transmission line parameter errors using SCADA and synchrophasor measurements
    Costa, Leonardo F.
    Giraldo, Juan S.
    Castro, Carlos A.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 135
  • [10] Generator Parameter Identification Using Time Series Model and PMU Measurements
    Zhou, Tinghui
    Zhao, Ligang
    Hong, Chao
    Huang, Guanbiao
    Zhen, Hongyue
    Wang, Changxiang
    Wu, Xiaoshan
    Jing, C.
    2021 IEEE 12TH INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS (PEDG), 2021,