Numerical simulation on solar collector and cascade heat pump combi water heating systems in Kazakhstan climates

被引:36
作者
Yerdesh, Ye. [1 ]
Abdulina, Z. [2 ]
Aliuly, A. [1 ,3 ]
Belyayev, Ye. [1 ,3 ]
Mohanraj, M. [4 ]
Kaltayev, A. [1 ,3 ]
机构
[1] Al Farabi Kazakh Natl Univ, Dept Mech, Alma Ata, Kazakhstan
[2] Satbayev Univ, Dept Robot & Engn Tools Automat, Alma Ata, Kazakhstan
[3] Satbayev Univ, Dept Appl Mech & Engn Graph, Alma Ata, Kazakhstan
[4] Hindusthan Coll Engn & Technol, Dept Mech Engn, Coimbatore, Tamil Nadu, India
关键词
Cascade heat pump; Solar collector; Kazakhstan climates; Numerical simulation; REFRIGERANT CHARGE; SINGLE-STAGE; PERFORMANCE; OPTIMIZATION; EVAPORATOR; R134A; PART;
D O I
10.1016/j.renene.2019.06.102
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
At low ambient temperatures, the heating capacity and coefficient of performance of a single stage vapour compression heat pump cycle is significantly getting reduced. The two stage cascade heat pump cycle operating with two different refrigerants provides a sustainable solution to lift the condenser temperature above 343 K. In this work, a numerical simulation model was developed for predicting the performance of a solar collector and two stage cascade heat pump combi water heating systems under Kazakhstan climatic conditions. The numerical simulation was performed for winter climatic conditions using nine refrigerant pairs such as, R32/R290, R32/R1234yf, R32/R134a, R410A/R290, R410A/R1234yf, R410A/R134a, R744/R290, R744/R1234yf and R744/R134a. The influences of solar irradiation, ambient temperature and condenser temperature are discussed. The solar collector and two stage heat pump combi heating system has about 30% energy savings when compared to the conventional two stage cascade heat pump without integration solar collectors. The R32/R290 refrigerant pair is having maximum coefficient of performance of 2.4 at 323 K condensing temperature and 263 K evaporating temperature. The refrigerant R744/R290 pair is identified as an environment friendly sustainable option in terms of its global warming impact for two stage cascade heat pump applications. (C) 2019 Published by Elsevier Ltd.
引用
收藏
页码:1222 / 1234
页数:13
相关论文
共 36 条
[1]  
Aliuly A, 2016, BULG CHEM COMMUN, V48, P135
[2]   Transcritical carbon dioxide heat pump systems: A review [J].
Austin, Brian T. ;
Sumathy, K. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (08) :4013-4029
[3]   Optimization of a CO2-C3H8 cascade system for refrigeration and heating [J].
Bhattacharyya, S ;
Mukhopadhyay, S ;
Kumar, A ;
Khurana, RK ;
Sarkar, J .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08) :1284-1292
[4]   Thermodynamic analysis and optimization of a novel N2O-CO2 cascade system for refrigeration and heating [J].
Bhattacharyya, Souvik ;
Garai, Anirban ;
Sarkar, Jahar .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05) :1077-1084
[5]   Energy evaluation of R152a as drop in replacement for R134a in cascade refrigeration plants [J].
Cabello, R. ;
Sanchez, D. ;
Llopis, R. ;
Catalan, J. ;
Nebot-Andres, L. ;
Torrella, E. .
APPLIED THERMAL ENGINEERING, 2017, 110 :972-984
[6]   Evaluation of the impacts of high stage refrigerant charge on cascade heat pump performance [J].
Chae, Jung-Hoon ;
Choi, Jong Min .
RENEWABLE ENERGY, 2015, 79 :66-71
[7]   Two-stage direct expansion solar-assisted heat pump for high temperature applications [J].
Chaturvedi, S. K. ;
Abdel-Salam, T. M. ;
Sreedharan, S. S. ;
Gorozabel, F. B. .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :2093-2099
[8]   Advances in heat pump systems: A review [J].
Chua, K. J. ;
Chou, S. K. ;
Yang, W. M. .
APPLIED ENERGY, 2010, 87 (12) :3611-3624
[9]  
Duffie JA, 2013, SOLAR ENGINEERING OF THERMAL PROCESSES, 4TH EDITION, P1, DOI 10.1002/9781118671603
[10]  
F-Chart Software, 2018, EES ENG EQ SOLV PROF