Identify Direct Lightning Strike Location Based on Discrete Wavelet Transform for 115-kV Transmission System

被引:2
作者
Chiradeja, Pathomthat [1 ]
Ngaopitakkul, Atthapol [2 ]
机构
[1] Srinakharinwirot Univ, Fac Engn, Bangkok 10110, Thailand
[2] King Mongkuts Inst Technol Ladkrabang, Sch Engn, Bangkok 10520, Thailand
来源
IEEE ACCESS | 2022年 / 10卷
关键词
Lightning; Transient analysis; Substations; Discrete wavelet transforms; Fault location; Transforms; Power transmission lines; lightning protection; lightning location; power system transients; transmission lines; travelling wave; FAULT-LOCATION; LINE; ALGORITHM; IDENTIFICATION; DISTANCE;
D O I
10.1109/ACCESS.2022.3195497
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper proposes three techniques for locating lightning strikes in a 115 kV transmission system over 88.5 km, based on the arrival time of a transient wave obtained from a discrete wavelet transform (DWT). The first technique calculates the location based on the 'type D' travelling wave method. The second technique analyses the first arrival time and same reflected-back wave arrival time between two substations. In the third technique, two sensors are installed to record arrival times at each sensor. Case studies of direct lightning strikes to phase conductors (shielding failure) are simulated using the 'Alternative Transients Program/Electromagnetic Transients Program' (ATP/EMTP). The influences of three parameters are considered: inception angles, the phase of the conductor, and the position at which the lightning struck the transmission system. By performing an operation scheme for all techniques, a positive sequence current is calculated, using a three-phase current from the ATP/EMTP program which is converted using Clark's transform. A positive sequence current is extracted to several scales using the DWT, and the orders of arrival times for both substations are determined. After the arrival times are obtained, each technique uses a different order of arrival time for calculating the lightning location. By comparing the average error among the three techniques, it is shown that the arrival time of the two sensors' technique is less than that of the other techniques.
引用
收藏
页码:80609 / 80622
页数:14
相关论文
共 55 条
  • [1] Induced voltages on overhead transmission lines because of nearby included lightning channel
    Abouzeid, Said I.
    Shabib, Gaber
    Mohamed, Adel Zein El Dein
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (13) : 1672 - 1680
  • [2] Critical aspects on wavelet transforms based fault identification procedures in HV transmission line
    Adly, Ahmed R.
    El Sehiemy, Ragab A.
    Abdelaziz, Almoataz Youssef
    Ayad, Nabil M. A.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (02) : 508 - 517
  • [3] A Fully Adaptive PMU-Based Fault Location Algorithm for Series-Compensated Lines
    Al-Mohammed, Ali H.
    Abido, M. A.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (05) : 2129 - 2137
  • [4] Wide-Band Modeling of Tower-Footing Grounding Systems for the Evaluation of Lightning Performance of Transmission Lines
    Alemi, Mohamad Reza
    Sheshyekani, Kehyan
    [J]. IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2015, 57 (06) : 1627 - 1636
  • [5] Advanced Rotor Fault Diagnosis for Medium-Voltage Induction Motors Via Continuous Transforms
    Antonino-Daviu, Jose A.
    Pons-Llinares, Joan
    Lee, Sang Bin
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2016, 52 (05) : 4503 - 4509
  • [6] Apisit C., 2013, IEEJ T POWER ENERGY, V133, P799
  • [7] BISCARO AAP, 2015, IEEE T POWER, V31, P428
  • [8] Chiradeja P, 2009, P IEEE INT C TRANSM, V1, P1
  • [9] Parameters of lightning strokes and their effects on power systems
    Chowdhuri, P
    [J]. 2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES, 2001, : 1047 - 1051
  • [10] Real-Time Detection of Transients Induced by High-Impedance Faults Based on the Boundary Wavelet Transform
    Costa, Flavio B.
    Souza, B. A.
    Brito, N. S. D.
    Silva, J. A. C. B.
    Santos, W. C.
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 5312 - 5323