Energy analysis of different configurations for a reversible ground source heat pump using a new flexible TRNSYS Type

被引:38
作者
Bordignon, Sara [1 ]
Emmi, Giuseppe [1 ]
Zarrella, Angelo [1 ]
De Carli, Michele [1 ]
机构
[1] Univ Padua, Dept Ind Engn, Appl Phys Sect, Via Venezia 1, I-35131 Padua, Italy
关键词
Heat Pump; Ground Source Heat Pumps; TRNSYS; REFPROP; Energy efficiency; Renewable Energy; PERFORMANCE; SYSTEM;
D O I
10.1016/j.applthermaleng.2021.117413
中图分类号
O414.1 [热力学];
学科分类号
摘要
TRNSYS Software is a flexible tool for dynamic simulation of plants, interconnecting the different components of the system represented as black boxes and called "Types". This paper presents a novel Type for the simulation of a reversible water-to-water heat pump that is freely released. Differently from the previous models available in this environment, the Type is based on the polynomials of the compressors and contains an internal link to REFPROP to easily evaluate the thermodynamic properties of refrigerant fluids. In the present work, the Type was employed for investigating a ground source heat pump providing space heating and cooling to a historic building, where, for architectural limitations, the existing high-temperature terminal units cannot be replaced. Its operation, using different refrigerants, was evaluated under three climates, simulating two heat pump configurations coupled with radiators or fan coils. In the first case, a cascade-cycle configuration was considered to supply high-temperature heat, whereas, with fan coils, a standard single-stage cycle was studied. The results for the cascade-cycle configuration showed a seasonal coefficient of performance ranging from 2.48 for the coldest location (Helsinki) to 2.86 for the warmest one (Athens). These values increased to 3.29 and 4.90, respectively, when considering fan coil terminal units instead of radiators. On the other hand, the seasonal efficiency values were equal to 7.95 in Helsinki and 5.56 in Athens. Moreover, the low incidence of the thermal drift effect on the long-term performance of the cascade ground source heat pump was highlighted, showing for the coldest location a penalisation of 2.5%, compared to 7.3% of the single-stage cycle.
引用
收藏
页数:20
相关论文
共 35 条
[1]  
[Anonymous], 2012, Transient System Simulation Tool
[2]  
[Anonymous], SUITE TOOLS FEATURES
[3]  
[Anonymous], 2019, ASHRAE HDB HVAC APPL
[4]  
[Anonymous], ENG EQUATION SOLVER
[5]   A review of performance of zero energy buildings and energy efficiency solutions [J].
Belussi, Lorenzo ;
Barozzi, Benedetta ;
Bellazzi, Alice ;
Danza, Ludovico ;
Devitofrancesco, Anna ;
Fanciulli, Carlo ;
Ghellere, Matteo ;
Guazzi, Giulia ;
Meroni, Italo ;
Salamone, Francesco ;
Scamoni, Fabio ;
Scrosati, Chiara .
JOURNAL OF BUILDING ENGINEERING, 2019, 25
[6]   Integration of renewable technologies in historical and heritage buildings: A review [J].
Cabeza, Luisa F. ;
de Gracia, Alvaro ;
Pisello, Anna Laura .
ENERGY AND BUILDINGS, 2018, 177 :96-111
[7]   Thermal analysis of a water source heat pump for space heating using an outdoor pool as a heat source [J].
Cardemil, J. M. ;
Schneider, W. ;
Behzad, M. ;
Starke, A. R. .
JOURNAL OF BUILDING ENGINEERING, 2021, 33
[8]   Geothermal heat pump in heating mode: Modeling and simulation on TRNSYS [J].
Chargui, R. ;
Sammouda, H. ;
Farhat, A. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (07) :1824-1832
[9]   A quasi-steady state mathematical model of an integrated ground source heat pump for building space control [J].
Corberan, J. M. ;
Finn, D. P. ;
Montagud, C. M. ;
Murphy, F. T. ;
Edwards, K. C. .
ENERGY AND BUILDINGS, 2011, 43 (01) :82-92
[10]   Assessment of heat pump with carbon dioxide/low-global warming potential working fluid mixture for drying process: Energy and emissions saving potential [J].
Dai, Baomin ;
Zhao, Pu ;
Liu, Shengchun ;
Su, Mingqiang ;
Zhong, Dan ;
Qian, Jiabao ;
Hu, Xiaowei ;
Hao, Ying .
ENERGY CONVERSION AND MANAGEMENT, 2020, 222