An approach to regulating the dc-link voltage of a voltage-source BTB system during power line faults

被引:38
作者
Hagiwara, M [1 ]
Akagi, H [1 ]
机构
[1] Tokyo Inst Technol, Dept Elect & Elect Engn, Tokyo 1528552, Japan
关键词
back-to-back (BTB) system; dc-link voltage regulation; line-frequency change; power flow control; power line faults;
D O I
10.1109/TIA.2005.853388
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A voltage-source back-to-back system for the purpose of achieving power flow control and/or line-frequency change in transmission systems has the attractive features of reliable and continuous operation, even during power line faults. However, an overvoltage appearing across the dc link during the faults should be limited to as low a value as possible because it does affect the power device ratings. This paper proposes a dc-link voltage regulator for effectively suppressing the overvoltage during power line faults. This regulator is characterized by compensating for a time delay inherent in each current controller, and for a power flow imbalance occurring during power line faults. The validity of the, proposed regulator is confirmed by theory and computer simulation.
引用
收藏
页码:1263 / 1271
页数:9
相关论文
共 15 条
[1]  
AHANG Z, 1993, IEEE T POWER DELIVER, V8, P712
[2]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[3]  
AREDES M, 2000, IEEJ IEEE IPEC TOK J, P1934
[4]  
ASLUND G, 2000, IEEE PES WINT M SING, V4, P2498
[5]   Analysis and design of a DC voltage-controlled static var compensator using quad-series voltage-source inverters [J].
Fujita, H ;
Tominaga, S ;
Akagi, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (04) :970-978
[6]   Performance of a self-commutated BTB HVDC link system under a single-line-to-ground fault condition [J].
Hagiwara, M ;
Fujita, H ;
Akagi, H .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (01) :278-285
[7]  
HINGORINI NG, 1999, UNDERSTANDING FACTS
[8]  
KIANG H, 1998, IEEE T POWER DELIVER, V13, P1278
[9]   The potential use of voltage-sourced converter-based back-to-back tie in load restorations [J].
Noroozian, M ;
Edris, AA ;
Kidd, D ;
Keri, AJF .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1416-1421
[10]   High-frequency impacts in a converter-based back-to-back tie;: The Eagle Pass installation [J].
Paulsson, L ;
Ekehov, B ;
Halén, S ;
Larsson, T ;
Palmqvist, L ;
Edris, AA ;
Kidd, D ;
Keri, AJF ;
Mehraban, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1410-1415