A Novel Approach Based on CEEMDAN to Select the Faulty Feeder in Neutral Resonant Grounded Distribution Systems

被引:41
作者
Jin, Tao [1 ,2 ]
Zhuo, Feng [1 ,2 ]
Mohamed, Mohamed A. [2 ,3 ]
机构
[1] Fujian Key Lab New Energy Generat & Power Convers, Fuzhou 350116, Peoples R China
[2] Fuzhou Univ, Dept Elect Engn, Fuzhou 350116, Peoples R China
[3] Menia Univ, Dept Elect Engn, Fac Engn, Al Minya 61519, Egypt
基金
中国国家自然科学基金;
关键词
Transient analysis; Circuit faults; Resistance; Oscillators; Sensitivity; Inductors; Complete ensemble empirical mode decomposition with adaptive noise (CEEMDAN); dominant mode; faulty feeder selection; transient component; transient zero-sequence current;
D O I
10.1109/TIM.2019.2954009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, a novel approach based on the complete ensemble empirical mode decomposition with adaptive noise (CEEMDAN) is proposed to solve the problems of adaptive extraction of fault signals' characteristics and the low sensitivity of faulty feeder selection methods. The key idea of this approach is to decompose the feeder's zero-sequence transient current by CEEMDAN into several modes of different frequency scales. The energy of each mode is calculated in order to obtain the fault characteristic mode. Then, the sum of characteristic mode components and its polarity are calculated. If the polarities of all feeders are the same, then the fault occurs on the bus. On the other hand, if the feeders' polarities are different, the sum of the characteristic mode components during one cycle is compared, and then, the fault occurs on the largest one. The proposed approach has been applied on different feeder structures, different fault types, and various perturbations for validation. Moreover, the outcomes of the proposed approach have been compared with the traditional EMD algorithm and wavelet transform (WT) method for further verification of its adaptation and sensitivity. The simulation results showed that the proposed approach can adaptively extract the fault characteristics and precisely distinguish the faulty and nonfaulty feeders. Furthermore, the simulation results assured that this approach is adaptable as it is not affected by perturbations, way of network operation, or feeder structure.
引用
收藏
页码:4712 / 4721
页数:10
相关论文
共 29 条
[1]  
[Anonymous], 2018, IEEE T INSTRUM MEAS, DOI DOI 10.1109/TIM.2018.2800978
[2]   EMD-Based signal filtering [J].
Boudraa, Abdel-Ouahab ;
Cexus, Jean-Christophe .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2007, 56 (06) :2196-2202
[3]   NOISE-ASSISTED EMD METHODS IN ACTION [J].
Colominas, Marcelo A. ;
Schlotthauer, Gaston ;
Torres, Maria E. ;
Flandrin, Patrick .
ADVANCES IN DATA SCIENCE AND ADAPTIVE ANALYSIS, 2012, 4 (04)
[4]   Hilbert-Transform-Based Transient/Intermittent Earth Fault Detection in Noneffectively Grounded Distribution Systems [J].
Cui, Tao ;
Dong, Xinzhou ;
Bo, Zhiqian ;
Juszczyk, Andrzej .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :143-151
[5]   Faulty feeder detection by adjusting the compensation degree of arc-suppression coil for distribution network [J].
Huang, Chun ;
Tang, Tao ;
Jiang, Yajun ;
Hua, Leng ;
Hong, Chen .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (04) :807-814
[6]  
Huijuan Zhang, 2010, Proceedings of the 2010 IEEE International Conference on Advanced Management Science (ICAMS 2010), P165, DOI 10.1109/ICAMS.2010.5553052
[7]   A Novel Adaptive EEMD Method for Switchgear Partial Discharge Signal Denoising [J].
Jin, Tao ;
Li, Qiangguang ;
Mohamed, Mohamed A. .
IEEE ACCESS, 2019, 7 :58139-58147
[8]  
[金涛 Jin Tao], 2015, [电工技术学报, Transactions of China Electrotechnical Society], V30, P96
[9]  
Li T., 2008, Power Syst. Technol, V32, P128
[10]   Application of signal processing and analysis in detecting single line-to-ground (SLG) fault location in high-impedance grounded distribution network [J].
Li, Yajie ;
Meng, Xiaoli ;
Song, Xiaohui .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (02) :382-389