On line PD measurements and diagnosis on power transformers

被引:35
作者
Aschenbrenner, D
Kranz, HG
Rutgers, WR
van den Aardweg, P
机构
[1] Berg Univ Wuppertal, High Voltage Lab, D-42097 Wuppertal, Germany
[2] KEMA T&D Consulting, NL-6800 ET Arnhem, Netherlands
关键词
partial discharge; UHF detection; PD pattern recognition;
D O I
10.1109/TDEI.2005.1430392
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
On line partial discharge (PD) measurements provide information on the dielectric integrity of the High Voltage insulation of oil insulated power transformers during service. These PD measurements are performed using a broadband antenna on an oil valve and UHF detection of PD signals. The sensitivity of this new detection technique is high and immunity for electromagnetic (EM) interference and corona discharges in air outside the transformer is very good. Dielectric faults can be detected in this way in an early stage of development and are classified in four categories. Automatic pattern recognition techniques of phase resolved Pulse sequence (PRPS) data are very useful in risk assessment of dielectric faults.
引用
收藏
页码:216 / 222
页数:7
相关论文
共 19 条
[1]  
ASCENBRENNER D, 2001, 12 ISH BANG IND
[2]  
ASCHENBRENNER D, 2002, 87 ETG DIAGN EL BETR, V87, P117
[3]  
ASCHENBRENNER D, 2001, 12 ISH BANG IND
[4]  
ASCHENBRENNER D, 2000, APPL AUTOMATED FAILU
[5]  
*CIGRE, 1999, CIGRE TF 15 33 03 05, P75
[6]  
*CIGRE, 1998, CIGRE WG 15 03 TASK, P87
[7]  
GROSSMAN E, 2001, P 12 ISH BANG
[8]  
HUECKER T, 1995, THESIS U WUPPERTAL G
[9]  
Judd M. D., 1999, Eleventh International Symposium on High Voltage Engineering (Conf. Publ. No.467), P362
[10]   Fundamentals in computer aided PD processing, PD pattern recognition and automated diagnosis in GIS [J].
Kranz, HG .