An Iterative Parameter-Free Fault Location Method on Three-Terminal Untransposed Transmission Lines

被引:0
|
作者
Lu, Dian [1 ]
Liu, Yu [1 ,2 ]
Lu, Dayou [1 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Minist Educ, Key Lab Control Power Transmiss & Convers, Shanghai 200240, Peoples R China
来源
2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM) | 2020年
关键词
Fault Location; Parameter-Free; Untransposed Line; Three-terminal lines; Synchrophasors;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an iterative parameter-free fault location algorithm on three-terminal untransposed transmission lines. Three phase voltage and current synchrophasor measurements at three terminals of the line before and during the fault are typically required. The proposed method considers the lumped shunt capacitance and does not require any assumption on the tower structure. The method first builds the transmission line models before and during faults, which describe all the physical laws that the line should obey. Meanwhile, the parameters of transmission line as well as the location of the fault are introduced as unknown variables. Afterwards, the fault location is obtained using the Newton-Raphson iterative method. Numerical experiments in PSCAD/EMTDC validate the fault location accuracy of the proposed method, which is independent of fault locations, fault types and fault impedances.
引用
收藏
页数:5
相关论文
共 50 条
  • [41] A Synchrophasor-Based Fault Location Method for Three-Terminal Hybrid Transmission Lines With One Off-Service Line Branch
    Lee, Yu-Ju
    Chao, Ching-Hsin
    Lin, Tzu-Chiao
    Liu, Chih-Wen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3249 - 3251
  • [42] New ground fault location method for three-terminal transmission line using unsynchronized current measurements
    Gaur, Vishal Kumar
    Bhalja, Bhavesh R.
    Saber, Ahmed
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 135
  • [43] One-end fault location method for untransposed four-circuit transmission lines
    Ngu, E. E.
    Ramar, K.
    Eisa, Amir
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) : 660 - 669
  • [44] A new fault location technique for three-terminal transmission grids using unsynchronized sampling
    Lin, Tzu-Chiao
    Xu, Zhi-Ren
    Ouedraogo, Faouzi Brice
    Lee, Yu-Ju
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 123
  • [45] Fault location of hybrid three-terminal HVDC transmission line based on improved LMD
    Gao, Shuping
    Xu, Zhenxi
    Song, Guobing
    Shao, Mingxing
    Jiang, Yuanyue
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 201
  • [46] Fault Location of Hybrid Three-terminal HVDC Transmission Line Based on Neural Network
    Li, Teng
    Han, Yuzhen
    Jiao, Zhijie
    Mu, Yong
    PROCEEDINGS OF 2019 IEEE 3RD INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC), 2019, : 1717 - 1722
  • [48] A Fault Location Algorithm Based on Circuit Analysis for Untransposed Parallel Transmission Lines
    Kang, Sang-Hee
    Ahn, Yong-Jin
    Kang, Yong-Cheol
    Nam, Soon-Ryul
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 1850 - 1856
  • [49] Genetic Algorithm Based Fault Locator Scheme for Three-Terminal Transmission Lines Using Asynchronous Measurements
    Hussain, Shoaib
    Osman, A. H.
    2015 6TH INTERNATIONAL CONFERENCE ON MODELING, SIMULATION, AND APPLIED OPTIMIZATION (ICMSAO), 2015,
  • [50] A New Fault Location Algorithm Based on Positive Sequence Current Difference for Double-circuit Three-terminal Transmission Lines
    Zhang S.
    Li Y.
    Chen X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2018, 38 (05): : 1488 - 1495