An Iterative Parameter-Free Fault Location Method on Three-Terminal Untransposed Transmission Lines

被引:0
作者
Lu, Dian [1 ]
Liu, Yu [1 ,2 ]
Lu, Dayou [1 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Minist Educ, Key Lab Control Power Transmiss & Convers, Shanghai 200240, Peoples R China
来源
2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM) | 2020年
关键词
Fault Location; Parameter-Free; Untransposed Line; Three-terminal lines; Synchrophasors;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an iterative parameter-free fault location algorithm on three-terminal untransposed transmission lines. Three phase voltage and current synchrophasor measurements at three terminals of the line before and during the fault are typically required. The proposed method considers the lumped shunt capacitance and does not require any assumption on the tower structure. The method first builds the transmission line models before and during faults, which describe all the physical laws that the line should obey. Meanwhile, the parameters of transmission line as well as the location of the fault are introduced as unknown variables. Afterwards, the fault location is obtained using the Newton-Raphson iterative method. Numerical experiments in PSCAD/EMTDC validate the fault location accuracy of the proposed method, which is independent of fault locations, fault types and fault impedances.
引用
收藏
页数:5
相关论文
共 20 条
[1]  
[Anonymous], C371142014 IEEE
[2]  
[Anonymous], P IEEE RUSS POW TECH
[3]   Fault location scheme for a multi-terminal transmission line using synchronized voltage measurements [J].
Brahma, SM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1325-1331
[4]   Fault location on a transmission line using synchronized voltage measurements [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1619-1622
[5]  
Chayawat C., 2019, WATER AIR SOIL POLL, V45, P50, DOI [DOI 10.1007/s11270-007-9372-6, DOI 10.1016/J.AMJMS.2021.03.001,00089-6]
[6]   Noniterative Parameter-Free Fault Location on Untransposed Single-Circuit Transmission Lines [J].
Dobakhshari, Ahmad Salehi .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (03) :1636-1644
[7]   Travelling wave based fault location for teed circuits [J].
Evrenosoglu, CY ;
Abur, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1115-1121
[8]   Precise Fault Location on Transmission Lines Using Ensemble Kalman Filter [J].
Fan, Rui ;
Liu, Yu ;
Huang, Renke ;
Diao, Ruisheng ;
Wang, Shaobu .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) :3252-3255
[9]   A NEW FAULT LOCATION TECHNIQUE FOR 2-TERMINAL AND 3-TERMINAL LINES [J].
GIRGIS, AA ;
HART, DG ;
PETERSON, WL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :98-107
[10]   Fault location using the distributed parameter transmission line model [J].
Gopalakrishnan, A ;
Kezunovic, M ;
McKenna, SM ;
Hamai, DM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) :1169-1174