Advancing New Techniques for UHF PD Detection and Localization in the Power Transformers in the Factory Tests

被引:83
作者
Mirzaei, H. R. [1 ]
Akbari, A. [1 ,2 ]
Gockenbach, E. [2 ]
Miralikhani, K. [3 ]
机构
[1] KN Toosi Univ Technol, Dept Elect Engn, Tehran 158754416, Iran
[2] Leibniz Univ Hannover, Hannover, Germany
[3] Iran Transfo Co, Zanjan, Iran
关键词
Partial discharge; power transformer; ultra-high frequency; UHF antenna; PARTIAL DISCHARGES; OPTIMIZATION; LOCATION;
D O I
10.1109/TDEI.2014.004249
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) detection in the ultra-high frequency (UHF) range is state of the art. One of the most critical points in this detection method is adopting proper and suitable antenna design. In this paper, a new design of UHF antennas is introduced which is suitable to be used on the transformers in the HV laboratories of the manufacturers. To ensure the applicability of the new antenna, experimental UHF PD measurements are carried out on a transformer tank model as well as on the real power transformers. Installing several UHF antennas on the transformer tank to perform defect localization is also an important issue. There are rigorous limitations and lack of the places to install the antennas. This problem is almost solved by using the mentioned new antenna design. The proper positioning of the antennas is the other critical point in the UHF method. Placing the antennas in improper positions will damage the localization accuracy. In this paper, an automatic algorithm is introduced to determine the best installation positions for the antennas to enhance the localization accuracy. The efficacy of this algorithm is investigated by using the results of experimental measurements on power transformers.
引用
收藏
页码:448 / 455
页数:8
相关论文
共 16 条
[11]   A Novel Method for Ultra-High-Frequency Partial Discharge Localization in Power Transformers Using the Particle Swarm Optimization Algorithm [J].
Mirzaei, Hasan Reza ;
Akbari, Asghar ;
Gockenbach, Ernst ;
Zanjani, Mojtaba ;
Miralikhani, Karim .
IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (02) :26-39
[12]   Experimental Comparison of UHF Sensor Types for PD Location Applications [J].
Pinpart, T. ;
Judd, M. D. .
2009 IEEE ELECTRICAL INSULATION CONFERENCE, 2009, :26-30
[13]   Comparative investigations on UHF and acoustic PD detection sensitivity in transformers [J].
Raja, K ;
Floribert, T .
CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, :150-153
[14]   Partial discharge location in power transformers using wideband RF detection [J].
Tang, Zhiguo ;
Li, Chengrong ;
Cheng, Xu ;
Wang, Wei ;
Li, Jinzhong ;
Li, Jun .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (06) :1193-1199
[15]   Partial Discharge Measurement in the Ultra High Frequency (UHF) Range [J].
Tenbohlen, S. ;
Denissov, D. ;
Hoek, S. M. ;
Markalous, S. M. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) :1544-1552
[16]  
Zanjani M, 2012, PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), P497, DOI 10.1109/CMD.2012.6416187