Experimental investigations on desiccant wheels

被引:62
作者
Eicker, Ursula [1 ]
Schuerger, Uwe [1 ]
Koehler, Max [1 ]
Ge, Tianshu [2 ]
Dai, Yanjun [2 ]
Li, Hui [2 ]
Wang, Ruzhu [2 ]
机构
[1] Univ Appl Sci, Res Ctr Zafh Net, D-70714 Stuttgart, Germany
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
Desiccative cooling; Desiccant wheels; Adsorption; Dehumidification; SILICA-GEL;
D O I
10.1016/j.applthermaleng.2012.03.005
中图分类号
O414.1 [热力学];
学科分类号
摘要
Experimental investigations on several commercially available and newly fabricated rotors are conducted in two different laboratories to evaluate performance trends. Experimental uncertainties are analysed and the parameters determining the rotor performance are investigated. It is found that the optimal rotation speed is lower for lithium chloride or compound rotors than for silica gel rotors. Higher regeneration air temperatures lead to higher dehumidification potentials at almost equal dehumidification efficiencies, but with increasing regeneration specific heat input and enthalpy changes of the process air. The influence of the regeneration air humidity was also notable and low relative humidities increase the dehumidification potential. Finally, the measurements show that rising water content in the ambient air causes the dehumidification capacity to rise, while the dehumidification efficiency is not much affected and both specific regeneration heat input and latent heat change of the process air decrease. For desiccant cooling applications in humid climates this is a positive trend. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:71 / 80
页数:10
相关论文
共 12 条
[1]   Desiccant wheel regenerated by thermal energy from a microcogenerator: Experimental assessment of the performances [J].
Angrisani, Giovanni ;
Capozzoli, Alfonso ;
Minichiello, Francesco ;
Roselli, Carlo ;
Sasso, Maurizio .
APPLIED ENERGY, 2011, 88 (04) :1354-1365
[2]  
[Anonymous], THESIS TU DARMSTADT
[3]  
[Anonymous], DEH ALL REQ INT PUBL
[4]  
[Anonymous], THESIS DE MONTFORT U
[5]   Kinetics of water sorption on SWS-1L (calcium chloride confined to mesoporous silica gel): Influence of grain size and temperature [J].
Aristov, YI ;
Glaznev, IS ;
Freni, A ;
Restuccia, G .
CHEMICAL ENGINEERING SCIENCE, 2006, 61 (05) :1453-1458
[6]   Performance analysis of four-partition desiccant wheel and hybrid dehumidification air-conditioning system [J].
Jeong, Jongsoo ;
Yamaguchi, Seiichi ;
Saito, Kiyoshi ;
Kawai, Sunao .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (03) :496-509
[7]   Practical thermal performance correlations for molecular sieve and silica gel loaded enthalpy wheels [J].
Jeong, JW ;
Mumma, SA .
APPLIED THERMAL ENGINEERING, 2005, 25 (5-6) :719-740
[8]   Use of compound desiccant to develop high performance desiccant cooling system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02) :345-353
[9]  
Kast W., 1988, Adsorption aus der Gasphase: Ingenieurwissenschaftliche Grundlagen und technische Verfahren
[10]   Heat and mass transfer in composite desiccant pore structures for dehumidification [J].
Majumdar, P .