Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers

被引:5
作者
Yuan, Xiaolei [1 ,2 ]
Zhou, Xuetao [2 ]
Liang, Yumin [2 ]
Pan, Yiqun [2 ]
Kosonen, Risto [1 ]
Lin, Zhongping [2 ]
机构
[1] Aalto Univ, Sch Mech Engn, Espoo 02150, Finland
[2] Tongji Univ, Sch Mech Engn, Shanghai 200092, Peoples R China
基金
芬兰科学院; 中国国家自然科学基金;
关键词
data centers; thermal environment; local hotspot; decentralized cooling system; heat pipe exchanger; DATA CENTER ENERGY; AIR; PERFORMANCE; MANAGEMENT;
D O I
10.3390/buildings12071015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposes a decentralized cooling system combined with a traditional computer room air conditioning unit and server-level heat pipe exchangers for thermal environment optimization in a data center. Two cooling strategies, with heat exchangers installed above and below the servers respectively, are proposed and compared with the original CRACs system in terms of thermal environment. The simulation results of the original data center model are in good agreement with the on-site measurement results, and thus its reliability can be validated. The results show that a decentralized cooling system can effectively improve the thermal environment in data centers. To obtain the highest cooling efficiency, altogether 18 cases, where heat pipe exchangers were installed at different locations and heights, are analyzed and compared. The results show that the thermal environment is optimal when heat pipe exchangers are installed 0.01 m below each server. The local hotspot temperature is reduced by 6.8 degrees C, and the temperature distribution of the rack is the most uniform, which can effectively reduce the heat accumulation in data centers.
引用
收藏
页数:19
相关论文
共 48 条
[1]   A parametric CFD study of computer room air handling bypass in air-cooled data centers [J].
Ahmadi, Vahid Ebrahimpour ;
Erden, Hamza Salih .
APPLIED THERMAL ENGINEERING, 2020, 166
[2]   Failure Analysis of Direct Liquid Cooling System in Data Centers [J].
Alkharabsheh, Sami ;
Puvvadi, Udaya L. N. ;
Ramakrishnan, Bharath ;
Ghose, Kanad ;
Sammakia, Bahgat .
JOURNAL OF ELECTRONIC PACKAGING, 2018, 140 (02)
[3]   A Brief Overview of Recent Developments in Thermal Management in Data Centers [J].
Alkharabsheh, Sami ;
Fernandes, John ;
Gebrehiwot, Betsegaw ;
Agonafer, Dereje ;
Ghose, Kanad ;
Ortega, Alfonso ;
Joshi, Yogendra ;
Sammakia, Bahgat .
JOURNAL OF ELECTRONIC PACKAGING, 2015, 137 (04)
[4]   Computational fluid dynamic investigation of liquid rack cooling in data centres [J].
Almoli, Ali ;
Thompson, Adam ;
Kapur, Nikil ;
Summers, Jonathan ;
Thompson, Harvey ;
Hannah, George .
APPLIED ENERGY, 2012, 89 (01) :150-155
[5]   Assessing ICT global emissions footprint: Trends to 2040 & recommendations [J].
Belkhir, Lotfi ;
Elmeligi, Ahmed .
JOURNAL OF CLEANER PRODUCTION, 2018, 177 :448-463
[6]   Thermodynamic analysis of hybrid cooling system integrated with waste heat reusing and peak load shifting for data center [J].
Chen, Hua ;
Peng, Yu-hang ;
Wang, Yan-ling .
ENERGY CONVERSION AND MANAGEMENT, 2019, 183 :427-439
[7]   Reliability and availability assessment and enhancement of water-cooled multi-chiller cooling systems for data centers [J].
Cheung, Howard ;
Wang, Shengwei .
RELIABILITY ENGINEERING & SYSTEM SAFETY, 2019, 191
[8]   Materials for thermal conduction [J].
Chung, DDL .
APPLIED THERMAL ENGINEERING, 2001, 21 (16) :1593-1605
[9]   Coupled inviscid-viscous solution method for bounded domains: Application to data-center thermal management [J].
Cruz, Ethan ;
Joshi, Yogendra .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 85 :181-194
[10]  
Dai J., 2014, Optimum cooling of data centers, DOI DOI 10.1007/978-1-4614-5602-5