Synchrophasor-Based Intelligent Autoreclosing Scheme for Series Compensated Transmission Lines

被引:21
作者
Gajare, Swaroop [1 ]
Pradhan, Ashok Kumar [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
关键词
Adaptive dead time; autorecloser; multicircuit transmission line; series compensation; synchronized measurements; NEURAL-NETWORK; SINGLE; ALGORITHM; RECLOSURE;
D O I
10.1109/TPWRD.2016.2613908
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In a transmission network, autoreclosing provides quick restoration of the line for transient faults and improves system stability. Autoreclosing during permanent fault may damage power system elements. This paper presents a method to block autoreclosing for permanent line-to-ground faults on multicircuit series compensated transmission line using synchronized measurements fromboth ends. The method utilizes measurements from the healthy phases of the line to calculate an index, which determines the persistence of a fault to control the reclosing. In the case of a transient line-to-ground fault, the index is high during the fault and zero after extinction of the secondary arc. The index can be used to modify the dead time of the recloser and thereby reclosing during fault (both transient and permanent) is prevented. The proposed method is tested using the sample data obtained from EMTDC/PSCAD simulation of an actual series compensated line in the Indian power grid. Results demonstrate the accuracy of the proposed method.
引用
收藏
页码:2255 / 2262
页数:8
相关论文
共 43 条
[1]   Effect of adaptive single-pole reclosing on the stochastic behavior of turbine-generator shift torsional torques [J].
Aboreshaid, S ;
Billinton, R ;
Faried, SO .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1998, 13 (02) :133-139
[2]   An alternative approach to adaptive single pole auto-reclosing in high voltage transmission systems based on variable dead time control [J].
Ahn, SP ;
Kim, CH ;
Aggarwal, RK ;
Johns, AT .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :676-686
[3]  
Ali AJ, 2013, 2013 FIRST INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRICAL, COMMUNICATION, COMPUTER, POWER, AND CONTROL ENGINEERING (ICECCPCE'13), P31, DOI 10.1109/ICECCPCE.2013.6998766
[4]  
[Anonymous], 2012, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators, IEEE Std C5791-2011 Revis, P1, DOI DOI 10.1109/IEEESTD.2012.6166928
[5]  
[Anonymous], COND TRANSM LIN
[6]  
[Anonymous], 2016, SEL551
[7]  
[Anonymous], TECHN PART ACSR PANT
[8]   New concept in transmission line reclosure using high-frequency fault transients [J].
Bo, ZQ ;
Aggarwal, RK ;
Johns, AT ;
Zhang, BH ;
Ge, YZ .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1997, 144 (04) :351-356
[9]  
Chen Z., 2003, P IEEE POW ENG SOC G, V4, P2121
[10]   An adaptive single pole autoreclosure based on zero sequence power [J].
Elkalashy, Nagy I. ;
Darwish, Hatem A. ;
Taalab, Abdel-Maksoud I. ;
Izzularab, Mohmmad A. .
ELECTRIC POWER SYSTEMS RESEARCH, 2007, 77 (5-6) :438-446