Steady-state operating conditions of very long EHVAC cable lines

被引:24
|
作者
Gatta, F. M. [1 ]
Geri, A. [1 ]
Lauria, S. [1 ]
Maccioni, M. [1 ]
机构
[1] Univ Roma La Sapienza, Dept Astronaut Elect & Energet Engn, I-00184 Rome, Italy
关键词
EHVAC cables; Power transmission; Cable ampacity; Shunt compensation; Voltage and reactive power control; Temporary overvoltages;
D O I
10.1016/j.epsr.2011.03.011
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the present paper the authors investigate steady-state capabilities of very long EHVAC underground cable lines, without intermediate compensating stations, installed in meshed networks. Analytical formulas of cable length-loading relationship are presented to this purpose. The study shows that, in optimal operating conditions, most of the ampacity of such long underground cable lines can be exploited for active power transmission. Non-optimal operating envelopes are studied, showing the effect of terminal voltages and line losses on cable utilization and evidencing limited derating under realistic hypotheses. A parametric analysis of loading limits and possible voltage violations along the cable is shown: a simple criterion for optimal utilization of lossy cable lines is also proposed. Line-end shunt compensation requirements for integration of long EHVAC cable lines in transmission networks are then specified. Studies performed for both ideal and real cables and shunt reactors show that active power transmission of 100 km long, 400 kV-50 Hz underground cable lines can attain 90% of their thermal limit, without intermediate compensating stations. Excess reactive power and temporary overvoltages are effectively controlled by line-end compensation around 90%. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1525 / 1533
页数:9
相关论文
共 50 条
  • [21] Steady-state analysis of multiconductor transmission lines
    Pipes, LA
    JOURNAL OF APPLIED PHYSICS, 1941, 12 (11) : 782 - 799
  • [22] Estimation of Attainment of Steady-State Conditions for Compounds With a Long Half-Life
    Krause, Andreas
    Lott, Dominik
    Dingemanse, Jasper
    JOURNAL OF CLINICAL PHARMACOLOGY, 2021, 61 (01): : 82 - 89
  • [23] Calculating Steady-State Operating Conditions for Doubly-Fed Induction Generator Wind Turbines
    Medina Padron, Jose Fernando
    Feijoo Lorenzo, Andres Elias
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (02) : 922 - 928
  • [24] Effects of surface texture on journal-bearing characteristics under steady-state operating conditions
    Tala-Ighil, N.
    Maspeyrot, P.
    Fillon, M.
    Bounif, A.
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART J-JOURNAL OF ENGINEERING TRIBOLOGY, 2007, 221 (J6) : 623 - 633
  • [25] THERMAL-HYDRAULIC MODELING OF THE STEADY-STATE OPERATING CONDITIONS OF A FIRE-TUBE BOILER
    Rahmani, Ahmed
    Dahia, Ahmed
    NUCLEAR TECHNOLOGY & RADIATION PROTECTION, 2009, 24 (01): : 29 - 37
  • [26] BEHAVIOR OF FISSION-GAS IN LWR FUEL DURING STEADY-STATE OPERATING-CONDITIONS
    REST, J
    TRANSACTIONS OF THE AMERICAN NUCLEAR SOCIETY, 1976, 23 (JUN18): : 171 - 172
  • [28] Influence of running-in operating conditions on the steady-state torque loss of ground spur gears
    Fernandes, Carlos M. C. G.
    Pais, Joao C.
    Martins, Ramiro C.
    Seabra, Jorge H. O.
    FORSCHUNG IM INGENIEURWESEN-ENGINEERING RESEARCH, 2021, 85 (02): : 567 - 582
  • [29] COMPUTATION OF STEADY-STATE OPERATING-CONDITIONS OF TURBO-ALTERNATORS TAKING SATURATION INTO ACCOUNT
    BADR, MAL
    BADR, MA
    KHALIFA, FA
    ELECTRIC MACHINES AND ELECTROMECHANICS, 1982, 7 (03): : 215 - 230
  • [30] Steady-state characteristics prediction of marine towing cable with BPNN
    Guo, Li
    Yuan, Yuchao
    Tang, Wenyong
    Xue, Hongxiang
    SHIPS AND OFFSHORE STRUCTURES, 2024, 19 (02) : 208 - 222