Principle and Control Design of a Novel Hybrid Arc Suppression Device in Distribution Networks

被引:32
作者
Fan, Bishuang [1 ]
Yao, Ganzhou [1 ]
Wang, Wen [1 ]
Zeng, Xiangjun [1 ]
Guerrero, Josep M. [2 ]
Yu, Kun [1 ]
Zhuo, Chao [1 ]
机构
[1] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Hunan Prov Key Lab Smart Grids Operat & Control, Changsha 410114, Peoples R China
[2] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
基金
中国国家自然科学基金;
关键词
Grounding; Voltage control; Distribution networks; Circuit faults; Inductance; Power supplies; Windings; dual-loop control; hybrid arc suppression; single line-to-ground (SLG) fault; SINGLE-PHASE; FAULTS;
D O I
10.1109/TIE.2021.3050390
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
A single line-to-ground (SLG) fault may lead to a more severe line-to-line fault and power supply interruption if the ground-fault current exceeds a certain value. Arc suppression device (ASD) is a good solution to eliminate the ground-fault current. A novel hybrid ASD is proposed in this article, which consists of a passive device and an active one. The passive device utilizes multiterminal breakers and an isolation transformer to couple a secondary voltage of a zig-zag grounding transformer to the neutral point to compensate the majority of the ground-fault current. The active device uses a single-phase voltage source inverter to eliminate the residual fault current due to the leakage inductance of the zig-zag grounding transformer in the passive device. A dual-loop voltage and current control method for the active device is designed for the accurate residual current compensation. Results of simulation and prototype experiment validate the effectiveness of the proposed hybrid ASD. The proposed hybrid ASD does not need to detect distributed line-to-ground parameters, and it has lower cost, less control complexity, higher reliability, and better performance, compared to other ASDs.
引用
收藏
页码:41 / 51
页数:11
相关论文
共 21 条
[1]  
[Anonymous], 2018, C571582017 IEEE
[2]   Minimising the risk of cross-country faults in systems using arc suppression coils [J].
Burgess, R. ;
Ahfock, A. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (07) :703-711
[3]   Ground Fault Temporary Overvoltages in MV Networks: Evaluation and Experimental Tests [J].
Cerretti, Alberto ;
Gatta, Fabio Massimo ;
Geri, Alberto ;
Lauria, Stefano ;
Maccioni, Marco ;
Valtorta, Giovanni .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1592-1600
[4]   Realization of active power filter based on indirect current control algorithm using Xilinx system generator for harmonic elimination [J].
Dash, Santanu Kumar ;
Panda, Gayadhar ;
Ray, Pravat Kumar ;
Pujari, Sashank Sekhar .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 74 :420-428
[5]   Effect of a lossy dispersive ground on lightning overvoltages transferred to the low-voltage side of a single-phase distribution transformer [J].
De Conti, Alberto ;
Oliveira, Vinicius C. ;
Rodrigues, Phelippe R. ;
Silveira, Fernando H. ;
Silvino, Jose L. ;
Alipio, Rafael .
ELECTRIC POWER SYSTEMS RESEARCH, 2017, 153 :104-110
[6]   Faulty phase recognition method based on phase-to-ground voltages variation for neutral ungrounded distribution networks [J].
Fan, Bishuang ;
Yao, Ganzhou ;
Wang, Wen ;
Yang, Xin ;
Ma, Haihang ;
Yu, Kun ;
Zhuo, Chao ;
Zeng, Xiangjun .
ELECTRIC POWER SYSTEMS RESEARCH, 2021, 190
[7]  
Gargoom A, 2018, IEEE POW ENER SOC GE
[8]  
IEEE RecommendedPractice forGrounding of Industrial and Commercial Power Systems, 2007, 1422007 IEEE
[9]   A Generalized Design Framework for Neutral Point Voltage Balance of Three-Phase Vienna Rectifiers [J].
Li, Xing ;
Han, Jian ;
Sun, Yao ;
Su, Mei ;
Lin, Jianheng ;
Xie, Shiming ;
Huang, Shoudao .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2019, 34 (10) :10221-10232
[10]   Zero-sequence voltage trajectory analysis for unbalanced distribution networks on single-line-to-ground fault condition [J].
Meng, Jun ;
Wang, Wen ;
Tang, Xin ;
Xu, Xianyong .
ELECTRIC POWER SYSTEMS RESEARCH, 2018, 161 :17-25