Improved schemes for traditional current-based phase selectors in wind power systems

被引:19
作者
Zhang, Jinhua [1 ]
Zhang, Baohui [1 ]
Wang, Chenqing [2 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] State Grid Jiangsu Elect Power Co Ltd, Res Inst, Nanjing 211103, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
wind power plants; power generation faults; electric impedance measurement; relay protection; power generation protection; traditional current-based phase selectors; wind power generation systems; phase-selection schemes; positive-to-negative sequence current branch coefficient ratio; PNSCBC ratio; relay location; weak-infeed systems; wind power side; negative-to-positive sequence impedance ratio; NPSI ratio; sequence current fault components; phase current difference fault components; backside system impedance; TCPS criteria; FAULT CLASSIFICATION; GENERATOR;
D O I
10.1049/iet-gtd.2018.5873
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study shows that traditional current-based phase-selection (TCPS) schemes are not applicable to wind power systems, and subsequently proposes two improved phase-selection schemes. On the basis of the practical TCPS criteria, derivations of the essential conditions for correct phase selection, which show that the positive-to-negative sequence current branch coefficient (PNSCBC) ratio at the relay location should be within a certain range, are presented. Wind power generation systems are weak-infeed systems; consequently, the PNSCBC ratio on the wind power side is approximately equal to the negative-to-positive sequence impedance (NPSI) ratio of the wind power system. However, the authors' theoretical and simulation analysis results show that the NPSI ratio of a wind power system may exceed the range required for reliable phase selection; therefore, TCPS schemes are not applicable to wind power systems. Thus, they propose improved phase-selection schemes based on sequence current fault components and phase current difference fault components. In the proposed schemes, the PNSCBC ratio is obtained using the backside system impedance measured by the relay, and it is then used for compensating the TCPS criteria. Simulation results and field fault test data verify the efficacy of the proposed schemes.
引用
收藏
页码:5781 / 5788
页数:8
相关论文
共 27 条
  • [1] An accurate fault classification technique for power system monitoring devices
    Adu, T
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (03) : 684 - 690
  • [2] [Anonymous], 2012, 2012 16 INT C OPTICA
  • [3] A combined directional and faulted phase selector element based on incremental quantities
    Benmouyal, G
    Mahseredjian, J
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) : 478 - 484
  • [4] A new approach to phase selection using fault generated high frequency noise and neural networks
    Bo, ZQ
    Aggarwal, RK
    Johns, AT
    Li, HY
    Song, YH
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) : 106 - 115
  • [5] Chen L, 2014, IEEE IJCNN, P1, DOI 10.1109/IJCNN.2014.6889506
  • [6] Fault Classification and Faulted-Phase Selection Based on the Initial Current Traveling Wave
    Dong, Xinzhou
    Kong, Wei
    Cui, Tao
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 552 - 559
  • [7] Ge Y., 2007, NEW TYPES PROTECTIVE
  • [8] Guanghui Li, 2011, 2011 IEEE International Conference on Advanced Power System Automation and Protection (APAP), P694, DOI 10.1109/APAP.2011.6180371
  • [9] He L., 2013, 2013 IEEE PES INN SM, P1
  • [10] Novel Fault Ride-Through Scheme and Control Strategy for Doubly Fed Induction Generator-Based Wind Turbine
    Huang, Po-Hsu
    El Moursi, Mohamed Shawky
    Hasen, Suud Ademnur
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2015, 30 (02) : 635 - 645