Assessing the vibrational frequencies of the Holweide Hospital in the city of Cologne (Germany) by means of ambient seismic noise analysis and FE modelling

被引:31
|
作者
Parolai, S [1 ]
Fäcke, A
Richwalski, SM
Stempniewski, L
机构
[1] Geoforschungszentrum Potsdam, D-14473 Potsdam, Germany
[2] Univ Karlsruhe, Inst Mass Bau & Baustofftechnol, Karlsruhe, TH, Germany
关键词
seismic noise; H/V spectral ratio; R/C building; FE modelling; resonance frequency; expansion joints;
D O I
10.1007/s11069-004-0686-z
中图分类号
P [天文学、地球科学];
学科分类号
07 ;
摘要
Ambient seismic noise measurements were conducted inside the Holweide Hospital (Cologne) for checking whether its frequencies of vibration fall into the range where soil amplification is expected. If this is the case, damage might increase in case of an earthquake due to an amplified structural response of the building. Two different techniques were used: the ratio between the horizontal and vertical components of the spectra recorded at stations located inside the building and the ratio between the corresponding components of the spectra recorded simultaneously inside the building and at a reference station placed outside. While the former method might be preferred because of less equipment involved, the latter has the advantage of producing more stable results and deleting automatically the influence of the sedimentary cover, which might obscure some eigenfrequencies of vibration of the building. An independently performed finite-element analysis of the hospital showed a good correlation between measured and calculated eigenmodes.
引用
收藏
页码:217 / 230
页数:14
相关论文
共 3 条