Optimization of air-conditioning system operating strategies for hot and humid climates

被引:29
作者
Huh, Jung-Ho [2 ]
Brandemuehl, Michael J. [1 ]
机构
[1] Univ Colorado, Boulder, CO 80309 USA
[2] Univ Seoul, Seoul 130743, South Korea
关键词
dehumidification; energy consumption; air-conditioning system; simulation; optimization;
D O I
10.1016/j.enbuild.2007.10.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper describes research into the optimal operation of building heating, ventilation, and air-conditioning (HVAC) systems focusing on both temperature and humidity control. While most previous work: on HVAC optimization has been limited to evaluation of conventional temperature-based control systems, this study emphasizes the humidity control issue in meeting both sensible and latent building loads. The analysis is based on a combination of a realistic simulation of a direct expansion (DX) air-conditioning system and a direct-search numerical optimization technique. The simulation models have been validated through comparisons with field data. Optimization was performed on five different system control variables to minimize system power consumption while meeting building loads and maintaining comfort. Indoor temperature and humidity are also optimized within standard comfort constraints. Building loads were modeled using an extended bin method that allows consideration of the interactions between loads and indoor conditions. Results indicate that minimum energy use typically occurs at low airflow rates, with indoor humidity levels below the upper comfort limit. Results also show that coil air bypass and evaporator circuiting control are typically not necessary unless operation would otherwise result in overcooling. The optimization results also translate to relatively simple strategies for system control. Significant savings are demonstrated over conventional control strategies used in packaged DX equipment. (C) 2007 Elsevier B.V. All rights reserved.
引用
收藏
页码:1202 / 1213
页数:12
相关论文
共 22 条
[1]  
[Anonymous], 2005, ASHRAE HDB FUND AM S
[2]  
*ARI, 1999, 5401999 ARI
[3]   A NEW METHOD OF CONSTRAINED OPTIMIZATION AND A COMPARISON WITH OTHER METHODS [J].
BOX, MJ .
COMPUTER JOURNAL, 1965, 8 (01) :42-52
[4]  
Brandemuehl M., 1993, HVAC 2 TOOLKIT ALGOR
[5]  
BRANDEMUEHL MJ, 1996, TR106065 EPRI
[6]   Optimal supply air temperature with respect to energy use in a variable air volume system [J].
Engdahl, F ;
Johansson, D .
ENERGY AND BUILDINGS, 2004, 36 (03) :205-218
[7]  
Harriman LG, 2002, ASHRAE J, V44, P22
[8]  
HENDERSON HI, 1992, ASHRAE TRAN, V98, P104
[9]  
HUGHES RR, 1972, MATH MODELS PROCESS
[10]  
HUH JH, 1995, THESIS U COLORADO BO