In-tube evaporation and condensation of R-22 and R-410A with plain and internally enhanced tubes

被引:14
作者
Bogart, J [1 ]
Thors, P [1 ]
机构
[1] Wolverine Tube Inc, Decatur, AL 35602 USA
关键词
in-tube; evaporation; condensation; enhanced surface; alternative refrigerants;
D O I
10.1615/JEnhHeatTransf.v6.i1.40
中图分类号
O414.1 [热力学];
学科分类号
摘要
Two-phase in-tube heat transfer and pressure drop comparisons for both evaporation and condensation were performed with R-22 and R-410A with a commercially available 9.53 mm internally enhanced tube - 60 internal ridges with 0.2 mm (0.008 ") ridge height and a helix angle of 18 degrees, The experiments were performed over appropriate mass flux ranges to ensure that the data were applicable for many uses: 100 - 400 kg/s-m(2) for the evaporation test and 200 - 800 kg/s-m(2) for the condensing tests. The R-22 evaporation data from Thors and Bogart (1994) is reprinted here for the comparison purposes and the balance of the data presented are new. The data indicate that R-410A has a substantially higher evaporation coefficient than R-22 over the bulk of the respective flow range and has a slightly higher condensation coefficient than R-22 over part of the respective flow range for a plain tube and a slightly lower condensation coefficient over the entire flow range for the enhanced tube. The results also show that R-410A has a substantially lower pressure drop than R-22 in both evaporation and condensation over the entire flow ranges.
引用
收藏
页码:37 / 50
页数:14
相关论文
共 6 条
[1]  
BRIGGS DE, 1968, 10 NAT HEAT TRANSF C
[2]  
MORITA H, 1993, 9335 INT TUB ASS
[3]  
Schlager L. M., 1989, RP469 ASHRAE
[4]  
SPATZ M, 1998, COMMUNICATION
[5]  
Thors P., 1994, J ENHANC HEAT TRANSF, V1, P365
[6]  
WIJAYA H, 1995, CH95142 ASHRAE