Filtration efficiency and loading characteristics of PM2.5 through commercial electret filter media

被引:62
作者
Tang, Min [1 ]
Thompson, Drew [1 ]
Chang, De-Qiang [2 ]
Chen, Sheng-Chieh [1 ]
Pui, David Y. H. [1 ]
机构
[1] Univ Minnesota, Particle Technol Lab, Mech Engn, 111 Church St SE, Minneapolis, MN 55455 USA
[2] Northeastern Univ, Coll Resources & Civil Engn, Filter Test Ctr, 3-11 Wenhua Rd, Shenyang 110819, Liaoning, Peoples R China
基金
美国国家科学基金会; 中国国家自然科学基金;
关键词
Health effect; HVAC system; Indoor air cleaner; Electret filtration; Unipolar charge; PM2.5; Filter loading; LONG-TERM PERFORMANCE; DUST-LOADED FIBER; COLLECTION EFFICIENCY; ULTRAFINE PARTICLES; AIR FILTRATION; SUBMICRON; EMISSION; AEROSOL; CHARGE; DEPOSITION;
D O I
10.1016/j.seppur.2017.11.067
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Atmospheric PM2.5 pollution has been attracting much public attention for decades because of its adverse health effects. China and other Asian countries are frequently exposed to high PM2.5 concentrations, and filtration techniques through HVAC systems and indoor air cleaners are often used to mitigate PM2.5 in indoor environments, e.g. commercial and residential buildings, schools, and hospitals. Electret filter media provide lower pressure resistance and are frequently used in air purification systems. However, existing test standards, e.g. ASHRAE 52.2-2012, only challenge filters with particles larger than 300 nm which makes it impossible to assess filter performance at the most penetrating particle size (MPPS) since the inherent MPPS of electret media is smaller than 100 nm. In this study for investigating the performance of the electret filter media against PM2.5, the filter media were first challenged with monodisperse particles of 3-500 nm (the majority of PM2.5 number concentration resides in this range) at face velocities of 0.05, 0.25 and 0.5 m s(-1) to obtain initial efficiency curves. Then the time-dependent efficiencies during the loading process were investigated using polydisperse NaCl particles which mimicked the size distribution of typical atmospheric PM2.5. Additionally, the effects of fiber charge and particle charge on initial efficiency and loading characteristics were evaluated by intentionally removing the fiber charges and charging the particles bipolarly (neutralized) or unipolarly. Results showed that the effects of fiber and particle charges on initial efficiency enhancement depended on particle sizes. The polarization force enhanced the collection of particles larger than similar to 20 nm particles, the image force enhanced the collection of particles smaller than similar to 100 nm, and the Columbic force enhanced the collection of particles smaller than similar to 300 nm. Charging the particles unipolarly can slow down the reduction of electrical efficiency during loading and enhance the minimum efficiency by 10-30% for 50-500 nm particles, compared to that of bipolarly charged particles. A model using an electric degradation parameter and mechanical collection efficiency raising factor was applied to explain the performance of electret media in loading processes.
引用
收藏
页码:101 / 109
页数:9
相关论文
共 41 条
[1]   Enhancement of the performance of low-efficiency HVAC filters due to continuous unipolar ion emission [J].
Agranovski, Igor E. ;
Huang, Ruth ;
Pyankov, Oleg V. ;
Altman, Igor S. ;
Grinshpun, Sergey A. .
AEROSOL SCIENCE AND TECHNOLOGY, 2006, 40 (11) :963-968
[2]  
[Anonymous], 121031 ISO
[3]  
ASHRAE, 2012, 522 ASHRAE ANSIASHRA
[4]  
Brown R. C., 1993, J AEROSOL SCI, DOI DOI 10.1016/0021-8502(95)90072-1
[5]   EFFECT OF INDUSTRIAL AEROSOLS ON THE PERFORMANCE OF ELECTRICALLY CHARGED FILTER MATERIAL [J].
BROWN, RC ;
WAKE, D ;
GRAY, R ;
BLACKFORD, DB ;
BOSTOCK, GJ .
ANNALS OF OCCUPATIONAL HYGIENE, 1988, 32 (03) :271-&
[6]  
CEN (Comite Europeen de Normalisation), 2012, EN 779
[7]   Capture of Sub-500 nm Particles Using Residential Electret HVAC Filter Media-Experiments and Modeling [J].
Chang, De-Qiang ;
Chen, Sheng-Chieh ;
Pui, David Y. H. .
AEROSOL AND AIR QUALITY RESEARCH, 2016, 16 (12) :3349-3357
[8]   Penetration of Sub-50 nm Nanoparticles Through Electret HVAC Filters Used in Residence [J].
Chang, De-Qiang ;
Chen, Sheng-Chieh ;
Fox, Andrew R. ;
Viner, Andrew S. ;
Pui, David Y. H. .
AEROSOL SCIENCE AND TECHNOLOGY, 2015, 49 (10) :966-976
[9]   Removal Efficiency of Bimodal PM2.5 and PM10 by Electret Respirators and Mechanical Engine Intake Filters [J].
Chen, Sheng-Chieh ;
Chang, De-Qiang ;
Pei, Chenxing ;
Tsai, Chuen-Jinn ;
Pui, David Y. H. .
AEROSOL AND AIR QUALITY RESEARCH, 2016, 16 (07) :1722-1729
[10]   Optimizing Filtration Experiments for Length and Fractal Dimension Characterization of Non- Spherical Particles [J].
Chen, Sheng-Chieh ;
Wang, Jing ;
Fissan, Heinz ;
Pui, David Y. H. .
AEROSOL SCIENCE AND TECHNOLOGY, 2015, 49 (08) :547-555