On Real-Time Detection of Line Sags in Overhead Power Grids Using an IoT-Based Monitoring System: Theoretical Basis, System Implementation, and Long-Term Field Verification

被引:18
作者
Jiang, Joe-Air [1 ,2 ]
Chiu, Huan-Chieh [1 ]
Yang, Yu-Cheng [1 ]
Wang, Jen-Cheng [3 ]
Lee, Chien-Hsing [4 ]
Chou, Cheng-Ying [1 ]
机构
[1] Natl Taiwan Univ, Dept Biomechatron Engn, Taipei 10617, Taiwan
[2] China Med Univ, China Med Univ Hosp, Dept Med Res, Taichung 40447, Taiwan
[3] Natl Taipei Univ Educ, Dept Comp Sci, Taipei 10671, Taiwan
[4] Natl Cheng Kung Univ, Dept Syst & Naval Mechatron Engn, Tainan 701, Taiwan
关键词
Transmission line measurements; Temperature measurement; Power transmission lines; Conductors; Monitoring; Temperature sensors; Sensors; Catenary; extra high-voltage (EHV) transmission systems; smart grids; temperature-dependent sags; triaxial accelerometer; TRANSMISSION-LINES; ENERGY MANAGEMENT; SENSOR PLACEMENT; WIND SPEEDS; TEMPERATURE; INTERNET;
D O I
10.1109/JIOT.2021.3139933
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
For overhead power grids, unexpected serious line sagging of extra-high voltage transmission lines would easily lead to major blackouts. Different direct and indirect sag measuring methods have been proposed, but they all have their own limitations. In this study, an Internet of Things (IoT)-based sag-monitoring system is proposed, which is able to perform real-time detection of line sags. The whole system has been deployed on two 161-kV lines for long-term field testing. The effectiveness of the proposed sag-monitoring system is verified through both theoretical calculation and field measurements. In this sag-monitoring system, a sag-sensing module is equipped with an embedded triaxial accelerometer to detect line sags at different spans of a single circuit. A catenary equation that takes temperature dependency into consideration is derived, so the measured accelerometer parameters can be converted to accurate line sag values. The long-term testing results show that the proposed sag-monitoring system yields an average error of 2.09%. The average differences between the sag values coming from the proposed system and a commercial sag measuring device are relatively small (between 0.57% and 4.14%), which proves that the sag values provided by the proposed system are reliable and accurate in the long-term testing. In addition, compared to the other existing sag measuring methods, the advantages of employing the proposed system are high measurement accuracy, and enabling wide field implementation, online monitoring, long-term field operation, and real-time transmission.
引用
收藏
页码:13096 / 13112
页数:17
相关论文
共 63 条
[1]  
Abraham AP, 2012, ANNU IEEE IND CONF, P1036
[2]  
Al-Ali A., 2015, Journal of Computer and Communications, V3, P229
[3]  
Anderson Patrick L., 2003, Working Paper 2003-2
[4]  
[Anonymous], 2010, COMM REQ SMART GRID
[5]  
[Anonymous], GEOGR TAIW
[6]  
[Anonymous], 2014, POW TRANSM OP MAN
[7]  
[Anonymous], ATMEGA48A PA 88A PA
[8]  
[Anonymous], AWK 6222 SER
[9]  
[Anonymous], BEAGLEBOARD XM SYST
[10]  
[Anonymous], 2012, 7382012 IEEE