Comparative analysis of domestic and feeder connected batteries for low voltage networks with high photovoltaic penetration

被引:7
作者
Hilton, George [1 ]
Cruden, Andrew [1 ]
Kent, Jeremy [2 ]
机构
[1] Univ Southampton, Fac Engn & Environm, Univ Rd, Southampton SO17 1BJ, Hants, England
[2] Swanbarton Ltd, Old Cake House, Pinkney SN16 0NX, Wilts, England
基金
英国工程与自然科学研究理事会;
关键词
Energy storage; Solar PV; Voltage violation; Thermal overload; Distribution network modelling; ENERGY-STORAGE; POWER TRANSFORMER; IMPACT; GENERATION; SYSTEMS; UNBALANCE; PROFILE;
D O I
10.1016/j.est.2017.07.019
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Excessive voltage and power flow issues associated with domestic solar power are threatening UK distribution system operation and the use of energy storage is one method proposed to mitigate these issues. In this study a data orientated approach was taken in order to simulate the effect of the location of the energy storage on the low voltage network. A number of small (< 15 kWh) domestic batteries were compared to a single larger (> 50 kWh) feeder connected battery in terms of their ability to shave load demand peaks, fill load demand valleys and counter voltage violations on a typical radial feeder system. To achieve this MatLab was used to create dispatch strategies for each battery and introduce them into an aggregated load, and OpenDSS was then used to model this scenario on a typical UK radial feeder based on the IEEE European Low Voltage Test Case. It was found that the feeder connected battery was more successful at mitigating the thermal overload effects of distributed generation at the low voltage level. Domestic batteries offer ease of installation and consumer support, likely to make their utilisation increasingly inevitable. However, their exposure to domestic energy flows and focus on minimising grid import to the home led to a reduced network level impact. This work shows that a feeder connected battery can respond to the power flows of the aggregated load and thus provides a far more capable tool for reducing network peak loads and preventing feeder system export. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:334 / 343
页数:10
相关论文
共 39 条
  • [1] AGORA Energiewende, 2013, AGORA ENERGIEWENDE 1
  • [2] Alam MJE, 2012, IEEE POW ENER SOC GE, DOI 10.1007/978-3-642-32639-4_1
  • [3] [Anonymous], 2008, CLIMATE CHANGE ACT
  • [4] [Anonymous], 2011, IEEE POW ENER SOC GE
  • [5] [Anonymous], 2016, W POWER DISTRIBUTION
  • [6] Ari GK., 2011, Clean Electrical Power (ICCEP), 2011 International Conference on, P744, DOI DOI 10.1109/ICCEP.2011.6036386
  • [7] A literature review on integration of distributed energy resources in the perspective of control, protection and stability of microgrid
    Basak, Prasenjit
    Chowdhury, S.
    Dey, S. Haider Nee
    Chowdhury, S. P.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (08) : 5545 - 5556
  • [8] Bollen M. H. J., 2002, IEEE Power Engineering Review, V22, P49, DOI 10.1109/MPER.2002.1045567
  • [9] Technical and economic design of photovoltaic and battery energy storage system
    Bortolini, Marco
    Gamberi, Mauro
    Graziani, Alessandro
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2014, 86 : 81 - 92
  • [10] Cappelle J., 2011, 2011 IEEE Second International Conference on Smart Grid Communications (SmartGridComm 2011), P534, DOI 10.1109/SmartGridComm.2011.6102380