DC-Link Capacitor Voltage Regulation for Three-Phase Three-Level Inverter-Based Shunt Active Power Filter with Inverted Error Deviation Control

被引:40
作者
Hoon, Yap [1 ]
Radzi, Mohd Amran Mohd [1 ]
Hassan, Mohd Khair [1 ]
Mailah, Nashiren Farzilah [1 ]
机构
[1] Univ Putra Malaysia, Dept Elect & Elect Engn, Fac Engn, Serdang 43400, Selangor, Malaysia
关键词
active power filter; current harmonics; fuzzy logic controller (FLC); inverted error deviation (IED); multilevel power converter; power electronics; power quality; REAL-TIME IMPLEMENTATION; FUZZY-LOGIC CONTROLLERS; NEUTRAL-POINT VOLTAGE; SPACE VECTOR PWM; REACTIVE POWER; MULTILEVEL INVERTERS; CONTROL STRATEGY; DESIGN; HARMONICS; COMPENSATION;
D O I
10.3390/en9070533
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A new control technique known as inverted error deviation (IED) control is incorporated into the main DC-link capacitor voltage regulation algorithm of a three-level neutral-point diode clamped (NPC) inverter-based shunt active power filter (SAPF) to enhance its performance in overall DC-link voltage regulation so as to improve its harmonics mitigation performances. In the SAPF controller, DC-link capacitor voltage regulation algorithms with either the proportional-integral (PI) or fuzzy logic control (FLC) technique have played a significant role in maintaining a constant DC-link voltage across the DC-link capacitors. However, both techniques are mostly operated based on a direct voltage error manipulation approach which is insufficient to address the severe DC-link voltage deviation that occurs during dynamic-state conditions. As a result, the conventional algorithms perform poorly with large overshoot, undershoot, and slow response time. Therefore, the IED control technique is proposed to precisely address the DC-link voltage deviation. To validate effectiveness and feasibility of the proposed algorithm, simulation work in MATLAB-Simulink and experimental implementation utilizing a TMS320F28335 Digital Signal Processor (DSP) are performed. Moreover, conventional algorithms with PI and FLC techniques are tested too for comparison purposes. Both simulation and experimental results are presented, confirming the improvement achieved by the proposed algorithm in terms of accuracy and dynamic response in comparison to the conventional algorithms.
引用
收藏
页数:25
相关论文
共 52 条
[1]  
Afghoul H., 2012, 2012 IEEE International Energy Conference (ENERGYCON 2012), P146, DOI 10.1109/EnergyCon.2012.6347742
[2]   Active harmonic filters [J].
Akagi, H .
PROCEEDINGS OF THE IEEE, 2005, 93 (12) :2128-2141
[3]  
[Anonymous], 2014, 519 IEEE
[4]  
Azevedo CC, 2011, BRAZIL POWER ELECTR, P877, DOI 10.1109/COBEP.2011.6085263
[5]   Fuzzy Logic Controller Based Three-Phase Shunt Active Power Filter for Compensating Harmonics and Reactive Power under Unbalanced Mains Voltages [J].
Belaidi, R. ;
Haddouche, A. ;
Guendouz, H. .
TERRAGREEN 2012: CLEAN ENERGY SOLUTIONS FOR SUSTAINABLE ENVIRONMENT (CESSE), 2012, 18 :560-570
[6]  
Bhalodi K. H., 2010, ACEEE INT J COMMUNIC, V1, P14
[7]  
Das Gupta U., 2015, 2015 International Conference on Electrical Engineering and Information Communication Technology (ICEEICT), P1, DOI [10.1109/ICEEICT.2015.7307338, DOI 10.1109/ICEEICT.2015.7307338]
[8]  
Dey P, 2014, 2014 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA), P481, DOI 10.1109/ISGT-Asia.2014.6873839
[9]  
Diwan S. P., 2011, ACEEE INT J ELECT PO, V2, P1
[10]   Active Power Filtering Using the ZDPC Method under Unbalanced and Distorted Grid Voltage Conditions [J].
Djazia, Kamel ;
Krim, Fateh ;
Chaoui, Abdelmadjid ;
Sarra, Mustapha .
ENERGIES, 2015, 8 (03) :1584-1605