Thermal buoyant smoke back-layering flow length in a longitudinal ventilated tunnel with ceiling extraction at difference distance from heat source

被引:89
作者
Chen, L. F. [1 ]
Hu, L. H. [1 ]
Zhang, X. L. [1 ]
Zhang, X. Z. [1 ]
Zhang, X. C. [1 ]
Yang, L. Z. [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
关键词
Tunnel; Ceiling extraction; Longitudinal ventilation; Thermally-driven smoke back-layering length; Heat source-extraction (opening) distance; POINT EXTRACTION; AIR-FLOW; FIRE; TEMPERATURE; MODEL;
D O I
10.1016/j.applthermaleng.2014.12.034
中图分类号
O414.1 [热力学];
学科分类号
摘要
Tunnel is a special long-narrow building structure. The thermal buoyancy-driven upstream reversing smoke back-layering flow produced by the burning of heat source is harmful for human evacuation. This paper reveals the effect of the distance between ceiling extraction (opening) distance and heat source on the thermally-driven smoke back-layering flow length beneath the ceiling in a tunnel with combination of ceiling extraction and longitudinal ventilation, which has not previously been reported. Experiments are conducted in a reduced-scale tunnel [72 m (length) x 1.5 m (width) x 1.3 m (height)]. A porous gas burner is used to provide steady heat source and its relative distance from the ceiling extraction (opening) is varied. It is found that the thermally-driven smoke back-layering flow length increases as the heat source-ceiling extraction (opening) distance increases. A new model is theoretically deduced to predict the smoke back-layering flow length including the factor of heat source-ceiling extraction (opening) distance, by accounting for the energy loss due to extraction which is calculated based on the local longitudinal temperature profile estimation. The predictions by the proposed model are in good agreement with the experimental results. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:129 / 135
页数:7
相关论文
共 24 条
  • [1] Convective heat transfer coefficients evaluation for a portable forced air tunnel
    Barbin, D. F.
    Neves Filho, L. C.
    Silveira, V.
    [J]. APPLIED THERMAL ENGINEERING, 2010, 30 (2-3) : 229 - 233
  • [2] The use of a closed-loop wind tunnel for measuring the combustion efficiency of flames in a cross flow
    Bourguignon, E
    Johnson, MR
    Kostiuk, LW
    [J]. COMBUSTION AND FLAME, 1999, 119 (03) : 319 - 334
  • [3] Studies on buoyancy driven two-directional smoke flow layering length with combination of point extraction and longitudinal ventilation in tunnel fires
    Chen, L. F.
    Hu, L. H.
    Tang, W.
    Yi, L.
    [J]. FIRE SAFETY JOURNAL, 2013, 59 : 94 - 101
  • [4] Oscillating behaviour of fire-induced air flow through a ceiling vent
    Chow, W. K.
    Gao, Y.
    [J]. APPLIED THERMAL ENGINEERING, 2009, 29 (16) : 3289 - 3298
  • [5] Measuring fire size in tunnels
    Guo, Xiaoping
    Zhang, Qihui
    [J]. APPLIED THERMAL ENGINEERING, 2013, 59 (1-2) : 101 - 105
  • [6] Studies on buoyancy-driven back-layering flow in tunnel fires
    Hu, L. H.
    Huo, R.
    Chow, W. K.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2008, 32 (08) : 1468 - 1483
  • [7] A non-dimensional global correlation of maximum gas temperature beneath ceiling with different blockage-fire distance in a longitudinal ventilated tunnel
    Hu, L. H.
    Tanga, W.
    Chen, L. F.
    Yi, L.
    [J]. APPLIED THERMAL ENGINEERING, 2013, 56 (1-2) : 77 - 82
  • [8] Longitudinal distributions of CO concentration and difference with temperature field in a tunnel fire smoke flow
    Hu, L. H.
    Tang, F.
    Yang, D.
    Liu, S.
    Huo, R.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (13-14) : 2844 - 2855
  • [9] Hu L.H., 2004, Journal of Applied Fire Science, V13, P53, DOI [10.2190/BQ02-N5TG-7TC7-TQFX, DOI 10.2190/BQ02-N5TG-7TC7-TQFX]
  • [10] Model scale tunnel fire tests with point extraction ventilation
    Ingason, Haukur
    Li, Ying Zhen
    [J]. JOURNAL OF FIRE PROTECTION ENGINEERING, 2011, 21 (01) : 5 - 36