Small-signal instability and supplementary coordinated damping-control of LCC-HVDC system with STATCOM under weak AC grid conditions

被引:17
作者
Guo, Chunyi [1 ]
Jiang, Wen [1 ]
Zhao, Chengyong [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing, Peoples R China
基金
美国国家科学基金会;
关键词
Line-Commutated-Converter based High; Voltage Direct Current Transmission (LCC-HVDC); STATCOM; Weak AC grid condition; Phase-Locked-Loop (PLL); Small-signal stability; Supplementary coordinated damping-control; DYNAMIC PERFORMANCE; INFEED HVDC; TRANSMISSION;
D O I
10.1016/j.ijepes.2018.06.055
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Static Synchronous Compensator (STATCOM) has been utilized to improve the dynamic behaviors of Line Commutated-Converter based High Voltage Direct Current (LCC-HVDC) system under weak AC grid conditions. However, the close coupling between STATCOM and LCC system could result in system instability especially under weak AC grid conditions, which has not been addressed in the existing literatures. This paper developed a linearized small-signal dynamic model of a LCC system with STATCOM at the inverter busbar, and validated its accuracy by comparing time-domain responses from small-signal model and simulation results from PSCAD/EMTDC. Based on the small-signal model, this paper investigated the impact of STATCOM on the small-signal stability margin of LCC-HVDC by eigen-analysis and participation factor methods. The results show that under weak AC grid conditions, the close interaction between the control system of STATCOM (especially the AC voltage controller) and PLL of LCC system, deteriorates the system stability and may cause oscillation/instability. Then, this paper proposed a novel supplementary coordinated damping-control (SCDC), for LCC-HVDC system with STATCOM under weak AC grid conditions. The results based on the eigen-analysis and electromagnetic transient (EMT) simulations indicate that the proposed SCDC approach can effectively mitigate the oscillations/instability induced by the controller interaction of STATCOM and LCC system, thus effectively improve the stability margin of the overall system.
引用
收藏
页码:246 / 254
页数:9
相关论文
共 16 条
[1]   Hybrid HVDC system for power transmission to island networks [J].
Andersen, BR ;
Xu, L .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1884-1890
[2]  
[Anonymous], 1997, IEEE Standard 1204-1997
[3]  
[Anonymous], 2011, THESIS
[4]  
[Anonymous], 10 INT C AC DC POW T
[5]   Impact of phase-locked loop on small-signal dynamics of the line commutated converter-based high-voltage direct-current station [J].
Guo, Chunyi ;
Zhao, Chengyong ;
Iravani, Reza ;
Ding, Hui ;
Wang, Xiaolin .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (05) :1311-1318
[6]   Analysis of Dual-Infeed HVDC With LCC-HVDC and VSC-HVDC [J].
Guo, Chunyi ;
Zhang, Yi ;
Gole, Aniruddha M. ;
Zhao, Chengyong .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1529-1537
[7]  
Kim C.K., 2009, IEEE TRANSMISSION DI, P1
[8]  
Kundur Prabha, POWER SYSTEM STABILI, p[356, 418]
[9]   DYNAMIC PERFORMANCE OF STATIC AND SYNCHRONOUS COMPENSATORS AT AN HVDC INVERTER BUS IN A VERY WEAK AC SYSTEM [J].
NAYAK, OB ;
GOLE, AM ;
CHAPMAN, DG ;
DAVIES, JB .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1350-1358
[10]   Commutation Failure Analysis in Multi-Infeed HVDC Systems [J].
Rahimi, Ebrahim ;
Gole, A. M. ;
Davies, J. B. ;
Fernando, Ioni T. ;
Kent, K. L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :378-384