Voltage Unbalance Emission Assessment in Radial Power Systems

被引:48
作者
Jayatunga, U. [1 ,2 ]
Perera, S. [1 ,2 ]
Ciufo, P. [1 ,2 ]
机构
[1] Univ Wollongong, Sch Elect Comp & Telecommun Engn, Wollongong, NSW 2522, Australia
[2] Endeavour Energy Power Qual & Reliabil Ctr, Wollongong, NSW 2522, Australia
关键词
Current unbalance; load asymmetry; power quality (PQ); system inherent asymmetry; voltage unbalance (VU); VU emission allocation; VU emission assessment;
D O I
10.1109/TPWRD.2012.2196294
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Voltage unbalance (VU) emission assessment is an integral part in the VU-management process where loads are allocated a portion of the unbalance absorption capacity of the power system. The International Electrotechnical Commission Report IEC/TR 61000-3-13:2008 prescribes a VU emission allocation methodology establishing the fact that the VU can arise at the point of common connection (PCC) due to upstream network unbalance and load unbalance. Although this is the case for emission allocation, approaches for post connection emission assessment do not exist except for cases where the load is the only contributor to the VU at the PCC. Such assessment methods require separation of the post connection VU emission level into its constituent parts. In developing suitable methodologies for this purpose, the pre and postconnection data requirements need to be given due consideration to ensure that such data can be easily established. This paper presents systematic, theoretical bases which can be used to assess the individual VU emission contributions made by the upstream source, asymmetrical line, and the load for a radial power system. The methodology covers different load configurations including induction motors. Assessments obtained by employing the theoretical bases on the study system were verified by using unbalanced load-flow analysis in MATLAB and using DIgSILENT Power Factory software.
引用
收藏
页码:1653 / 1661
页数:9
相关论文
共 14 条
[1]  
CIGRE/CIRED, 2011, 468 CIGRE CIRED C4 1
[2]   Negative phase-sequence voltages on E&W transmission system [J].
Emin, Z ;
Crisford, DS .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1607-1612
[3]  
*INT EL COMM, 1996, 6100036 IECTR
[4]  
International Electrotechnical Commission, 1996, 6100037 IECTR
[5]  
International Electrotechnical Commission, 2008, 61000313 IECTR
[6]  
Krause PC, 2002, ANAL ELECT MACHINERY, P165
[7]  
Kundur P., 1993, POWER SYSTEM STABILI, P271
[8]  
Mayordomo JG, 1996, EUR T ELECTR POWER, V6, P381, DOI 10.1002/etep.4450060603
[9]  
PARANAVITHANA P, 2008, 13 INT C HARM QUAL P
[10]  
Paranavithana P., 2009, THESIS U WOLLONGONG