A numerical analysis of cooling water temperature of two-stage adsorption chiller along with different mass ratios

被引:31
作者
Farid, S. K. [1 ]
Billah, M. M. [2 ]
Khan, M. Z. I. [3 ]
Rahman, M. M. [3 ]
Sharif, Uddin Md. [4 ]
机构
[1] Mirpur Girls Ideal Lab Inst, Dhaka 1216, Bangladesh
[2] Ahsanullah Univ Sci & Technol, Dept Arts & Sci, Dhaka 1208, Bangladesh
[3] Bangladesh Univ Engn & Technol, Dept Math, Dhaka 1000, Bangladesh
[4] Jahangirnagar Univ, Dept Math, Dhaka, Bangladesh
关键词
Reheat two-stage chiller; COP; Adsorption cycle; Silica gel/water; REFRIGERATION CYCLE; PERFORMANCE; CAPACITY; SYSTEM;
D O I
10.1016/j.icheatmasstransfer.2011.05.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper deals with the performance investigation of a silica gel/water based on two-stage, four-bed adsorption chiller with different mass allocation between upper and lower beds employing the re-heat scheme. The innovative chiller is powered by waste heat or renewable energy source of temperature between 50 degrees C and 90 degrees C with a coolant of inlet temperature 30 degrees C for air conditioning purpose. The performance of the four-bed adsorption chiller employing the re-heat scheme is compared with that of the two-stage conventional chiller with the re-heat scheme using equal mass allocation. Results show that cooling capacity can be improved with the optimum allocation of adsorbent mass to the upper beds than that of lower beds. Besides, it is observed that the cooling capacity can be improved up to 10.78% while the cooling water temperature is at 20 degrees C. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1086 / 1092
页数:7
相关论文
共 13 条
  • [1] Mass recovery adsorption refrigeration cycle-improving cooling capacity
    Akahira, A
    Alam, KCA
    Hamamoto, Y
    Akisawa, A
    Kashiwagi, T
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (03): : 225 - 234
  • [2] ALAM KCA, 2003, P 21 INT C REFR CD R
  • [3] Boelman EC, 1995, ASHRAE TRAN, V101, P358
  • [4] Critoph R. E., 1986, International Journal of Ambient Energy, V7, P183, DOI 10.1080/01430750.1986.9675500
  • [5] ACTIVATED CARBON ADSORPTION CYCLES FOR REFRIGERATION AND HEAT PUMPING
    CRITOPH, RE
    [J]. CARBON, 1989, 27 (01) : 63 - 70
  • [6] THE DYNAMICS OF A SOLID-ADSORPTION HEAT-PUMP CONNECTED WITH OUTSIDE HEAT-SOURCES OF FINITE-CAPACITY
    KARAGIORGAS, M
    MEUNIER, F
    [J]. HEAT RECOVERY SYSTEMS & CHP, 1987, 7 (03): : 285 - 299
  • [7] Kashiwagi T, 2002, PROCEEDINGS OF THE INTERNATIONAL SORPTION HEAT PUMP CONFERENCE, P50
  • [8] Performance evaluation of multi-stage, multi-bed adsorption chiller employing re-heat scheme
    Khan, M. Z. I.
    Alam, K. C. A.
    Saha, B. B.
    Akisawa, A.
    Kashiwagi, T.
    [J]. RENEWABLE ENERGY, 2008, 33 (01) : 88 - 98
  • [9] Study on a re-heat two-stage adsorption chiller - The influence of thermal capacitance ratio, overall thermal conductance ratio and adsorbent mass on system performance
    Khan, M. Z. I.
    Alam, K. C. A.
    Saha, B. B.
    Akisawa, A.
    Kashiwagi, T.
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (10) : 1677 - 1685